Chapter 3. Machine Adjustment Procedure | VFD-VJ 
 
3-16
Selection of multi-function display 
Setting value   
of Pr.00-04 
25: display the signal value of the analog input terminal OI with 0~10V 
mapped to 0~100% 
  Send the 100% flow rate through the controller and then check the multi-function display page 
to enter this value into Pr. 00-17 
  Send the 50% flow rate through the controller and then check the multi-function display page 
to enter this value into Pr. 00-18 
  Send the 0% flow rate through the keypad panel and then check the multi-function display 
page to enter this value into Pr.00-19 
Step 5. Bleed the circuit and make sure if there is any plastic material in the barrel. 
The machine can start operation only when there are no plastic materials inside the 
barrel. 
  Pr. 00-09 = 1 for pressure control mode 
Pressure control mode 
Setting value   
of Pr.00-09 
0: Speed control 
1: Pressure control   
  Set Pr.01-05 & Pr.01-06 = 0 second 
Acceleration time setting 
Setting value   
of Pr.01-05 
0.00 – 600.00 seconds 
Deceleration time setting 
Setting value   
of Pr.01-06 
0.00 – 600.00 seconds 
  When the air is bleeding completely, if there is any pressure fluctuation during operation, 
please adjust the pressure control Parameter PI in accordance with the method described in 
the “Description of Parameters”. 
Step 6. Send operation command though the controller 
  Pr.01-01=1 
Source of operation command 
Setting value   
of Pr. 01-01 
0: Operation by using the digital keypad 
1: Operation by using the external terminals. The Stop button on the 
keypad is disabled. 
2: Communication using RS-485. The Stop button on the keypad is 
disabled 
Step 7. Adjustment for injection/pressure holding 
  Heat up the barrel to the required temperature and set the controller in manual control mode.   
  Set the Ki values for the three stages PI to 0 (Pr.00-21, Pr.00-23 , and Pr.00-25) and Kp values 
to small values ( 50.0)≦