Chapter 4 Description of Parameters | VFD-VJ 
 
4-21
4-2 Description of Parameter Settings 
00 System Parameters   You can set this parameter during operation. 
 
 
Hybrid servo drive model code ID 
 
Control mode 
VF  FOCPG 
FOCPM 
 
  Factory setting: Read only 
 
 
Settings Read only 
 
 
Display of rated current of the hybrid servo drive 
 Control mode 
VF  FOCPG 
FOCPM 
 
  Factory setting: Read only 
 
Settings Read only 
  Pr.00-00 is to determine the capacity of the hybrid servo motor, which has been configured in this 
parameter in factory. In addition, the current value of Pr.00-01 can be read out to check if it is the rated 
current of the corresponding model.
 
Display value of the current value of Pr.00-01 for the related Pr.00-00. 
 
230V Models 
Power (KW) 
5.5  7.5  11  15 18.5 22  30  37 
Horse Power (HP) 
7.5 10 15 20 25 30 40 50 
Model ID 
12 14 16 18 20 22 214 215 
460V Models 
Power (KW) 
5.5 7.5 11 15 18.5 22 30 37 45 55 75 
Horse Power (HP) 
7.5 10 15 20 25 30 40 50 60 75 100 
Model ID 
13  15  410 411 412 413 414 415 416 417 418 
 
 
Reset parameter settings 
 Control mode 
VF  FOCPG  FOCPM   
  Factory setting: 0 
 
Settings 
0: No function 
1: Parameter Locked 
 
 
5: Rest the kWh at drive stop 
7: Reset CANopen index 
 
  10: Reset all the parameters to factory setting   
 . 
 
 
Software version 
 Control mode 
VF  FOCPG  FOCPM   
  Factory setting: #. ## 
 
Settings 
Read only 
 
 
 
Selection of multi-function display 
 Control mode 
VF  FOCPG  FOCPM   
  Factory setting: 0 
 
Settings  0: Display the output current (A) 
U
 
 
 
1: Reserved 
 
 
 
2: Display the actual output frequency (H) (unit: Hz) 
U
 
 
 
3: Display the DC bus voltage (U) (unit: V) 
U
 
 
 
4: Display the three-phase U, V, W output voltage (E) (unit: V) 
U