NO.5 Function List
22
pump
P133
High-speed operating time
1-250s
60
P134
Low-speed operating time
1-250s
60
P135
Stop pressure level
1-150%
95
P136
Stop level continuous time
1-250s
30
P137
Wake-up level
1-150%
80
P138
Sleep frequency
0.00-400.0Hz
20.00
P139
Continuous time of sleep
frequency
1-250s
20
P140
Reserve
5.8 Motor function parameters
Function
code
Function description
Setting range and
function description
Ex-factory
value
Alteration
P141
P142
P143
P144
Rated voltage of motor
Rated current of motor
Number of motor poles
Rated rotating speed of
motor
Set as per motor
nameplate
Set as per motor
nameplate
02-22
00-9999
*
*
04
1440
P145
Automatic torque
compensation
0.0-10.0%
2.0
P146
Motor no-load current
0-100%
40
P147
Motor slip compensation
0-1.0
0.000
P148-P149
Reserve
P150
AVR function
0-1
1
P151
Automatic energy-saving
function
0.0-20.0%
0.0
P152
Fault restart time
0.2-25.0s
1.0
P153
P154
P155
Selection of transient
stop restart
Allowed power fault time
Times of fault restart
0: Invalid 1: Frequency
tracking
0.1-5.0s
0-10
0
0.5
00
5.9 PID function parameters
Function
code
Function name
Setting range and content
description
Ex-factory
value
Alteration
P156
Proportional constant P
0.0-1000.0%
100.0

Table of Contents