ф Never forget to confirm the engine is in a stop.
(2) Open th right side door and remove the protection cover of the control panel. The
voltage change-over board is located on a right side of the control box.
Select the output voltage by setting the change- over plates as shown in the previous
page. Setting for 400 V or the like will make a surplus. To prevent them from missing,
pile and tighten the plates.
ф Turn the change-over switch on the voltage change-over board to the voltage you
require.
(S> Mount the protection cover and close and lock the side door.
[Note] Incorrect reconnection of the change over plates may cause a burning accident
in the generator. For reconnection, be sure to tighten the plates to prevent the
burning accident
Be sure to mount the protection cover before starting engine again.