DGBOX
rev. 1602
Inverter electronic control panels
for single pumps or pumping units
OPERATOR’S AND MAINTENANCE MANUAL
Model V in V out A P (kW) P (HP)
DGB MV 30
3 ~ 400V 3 ~ 400V
8 3 4
DGB MV 55
3 ~ 400V 3 ~ 400V
14 5,5 7,5
DGB MV 75
3 ~ 400V 3 ~ 400V
18 7,5 10
DGB MVF 30
3 ~ 400V 3 ~ 400V
8 + 8 3 + 3 4 + 4
DGB MVF 55
3 ~ 400V 3 ~ 400V
14 + 14 5,5 + 5,5 7,5 + 7,5
DGB MVF 75
3 ~ 400V 3 ~ 400V
18 + 18 7,5 + 7,5 10 + 10
DGB MW 30
3 ~ 400V 3 ~ 400V
8 + 8 3 + 3 4 + 4
DGB SV 30
3 ~ 400V 3 ~ 400V
8 3 4
DGB SV 55
3 ~ 400V 3 ~ 400V
14 5,5 7,5
DGB SV 75
3 ~ 400V 3 ~ 400V
18 7,5 10
10154507A .03 - 170530
EN

Questions and Answers

  • M
    Matthew JacksonAug 18, 2025
    What to do if the DGFLOW Control Panel shows OVER VOLTAGE?
    • B
      Bethany AlexanderAug 18, 2025
      If the DGFLOW Control Panel displays 'OVER VOLTAGE', it means the inverter power voltage is too high (over +15%). You should check the supply voltage.
  • A
    Antonio RodriguezAug 20, 2025
    What causes UNDER VOLTAGE on a DGFLOW Control Panel?
    • A
      Alex DoyleAug 20, 2025
      If the DGFLOW Control Panel displays 'UNDER VOLTAGE', it indicates that the inverter power voltage is too low (under -15%). To resolve this, check the supply voltage and the section and length of the inverter power cables.
  • D
    Daniel WangAug 25, 2025
    How to fix OVER TEMP MOD error on DGFLOW Control Panel?
    • M
      Mary OrtegaAug 26, 2025
      If the DGFLOW Control Panel displays 'OVER TEMP MOD', the inverter module is overheating. Ensure the air cooling channels are free, the fans are working, the ambient temperature is below 45°C, and the maximum operating current is within limits.
  • A
    alyssa50Aug 27, 2025
    What does OVER TEMP CAP mean on my DGFLOW Control Panel?
    • D
      Derek HendersonAug 28, 2025
      If the DGFLOW Control Panel displays 'OVER TEMP CAP', the inverter capacitors are overheating. Ensure the air cooling channels are free and that the fans are working. Also, check that the ambient temperature is not above 45°C and verify the maximum operating current.
  • C
    cunninghamjudyAug 30, 2025
    What causes OVER TEMP BOX error on DGFLOW Control Panel?
    • C
      christine58Aug 30, 2025
      If the DGFLOW Control Panel displays 'OVER TEMP BOX', it means the inverter is overheating internally. You should ensure the air cooling channels are free, the fans are working correctly, and the ambient temperature is not exceeding 45°C. Also, check the maximum operating current.
  • J
    Jade KellySep 1, 2025
    What does LOW PRESS mean on my DGFLOW Control Panel?
    • W
      Walter CherrySep 1, 2025
      If the DGFLOW Control Panel indicates 'LOW PRESS', and you're using a flow sensor, it means either the working pressure is near zero or the pump can't reach the set pressure. Check the pipes for leaks, verify the pressure sensor's operation, ensure the maximum pump pressure exceeds the set pressure, and inspect the pump for wear or obstructions.
  • L
    Lisa OlsenSep 3, 2025
    What to do if the FIXED SPEED pump fails to start on my DGFLOW Control Panel?
    • J
      Jeffrey SandovalSep 3, 2025
      If the FIXED SPEED pump fails to start, it could be due to the ammeter cutout tripping because the pump is drawing too much current. Check the current absorption at maximum load, verify the ammeter setting, and check the voltage at the pump terminals under load.
  • A
    april29Sep 5, 2025
    What does EXT OFF mean on my DGFLOW Control Panel?
    • A
      Aaron JohnsonSep 6, 2025
      If the DGFLOW Control Panel shows 'EXT OFF', it means the inverter is out of service due to an external signal. You should check the external signal to resolve this issue.
  • C
    Cynthia PhillipsSep 8, 2025
    Why does my DGFLOW Control Panel pump run constantly?
    • J
      Jennifer GriffinSep 8, 2025
      If the DGFLOW Control Panel's pump runs constantly when not needed, it could be due to system leaks, a faulty pressure sensor, a low 'switch off frequency' setting, or a flow rate sensor issue. Find and fix any leaks, inspect the pressure sensor, increase the switch off frequency setting, and inspect the flow sensor.
  • J
    Jacqueline SpencerSep 10, 2025
    Why does the DGFLOW Control Panel's pump stop too soon?
    • M
      Mr. Michael MartinezSep 12, 2025
      If the pump stops too soon when requested, it could be due to a high switch off frequency setting or a fault with the flow rate sensor. Try setting a lower switch off frequency and inspecting the flow sensor.

Summary

Safety Standards

Installation Guide

Description of Main Components

Input and Output Signal Connections

Starting Up the System

Self-Learning Configuration

Main Menu and Parameter Configuration

Base Setup Configuration

Core configuration parameters for initial setup.

Advanced Setup Configuration

Advanced parameters for optimizing system operation.

Hardware Setup Configuration

Configuration of signal inputs, outputs, and sensors.

Operation Parameter Settings

System Pressure and Rated Current Setup

Configuring system pressure and pump 1 rated current.

Checking Motor Rotation Direction

Motor Frequency and Operation Settings

Functional Test Mode

Alarm and Fault Management

Device Operating Modes

Configuration Mode

Accessing and modifying system parameters.

Base Setup Configuration Details

Advanced Setup Configuration Details

Hardware Setup Configuration Details

Maintenance Menu

Functional Test Procedures

Work Mode Operation Details

Out of Service Mode Details

Startup Procedure

Troubleshooting and Fault Resolution