Manuel d’installation & Mode d’emploi
PASRW030
PASRW040
PASRW045
PISCINE
THERMOPOMPE

Questions and Answers

  • S
    Sarah MitchellAug 9, 2025
    What to do if the temperature differential between water-in and water-out is too large in my Distinction PASRW040?
    • H
      Haley DavisAug 9, 2025
      If the temperature difference between the water entering and exiting your Distinction Heat Pump is too large, it may be due to insufficient water flow or low water pressure difference. You should check the water flow volume and inspect the system for any obstructions.
  • W
    William WigginsAug 15, 2025
    What to do if my Distinction Heat Pump shows an ambient sensor failure?
    • W
      William BarrettAug 16, 2025
      If your Distinction Heat Pump displays an ambient sensor failure, it's likely because the sensor has an open or short circuit. To resolve this, check or replace the sensor.
  • A
    Amanda ShermanAug 20, 2025
    What to do if my Distinction Heat Pump indicates a coil sensor failure?
    • L
      Leslie DodsonAug 20, 2025
      If your Distinction Heat Pump is showing a coil sensor failure, the cause might be an open or short circuit in the sensor. You should check or change the sensor to fix this.
  • E
    Eric RiceAug 27, 2025
    What to do if my Distinction Heat Pump displays a water outlet temp. sensor failure?
    • G
      gomezkatherineAug 27, 2025
      If your Distinction Heat Pump reports a water outlet temperature sensor failure, it could be caused by an open or short circuit in the sensor. The suggested solution is to check or change the sensor.
  • B
    brayadamSep 2, 2025
    What to do if my Distinction PASRW040 Heat Pump shows a water inlet temp. sensor failure?
    • M
      michaelgouldSep 2, 2025
      If your Distinction Heat Pump is experiencing a water inlet temperature sensor failure, it is probably because the sensor has an open or short circuit. You can try checking or changing the sensor to fix the problem.

Summary

INSTALLATION AND CONNECTION

3.2 Swimming Pool Heat Pump Location

Details optimal outdoor location factors for the heat pump.

3.4 Swimming Pool Heat Pump Plumbing

Explains plumbing requirements and connections for the heat pump.

3.5 Electrical Wiring Guide

Guides on electrical connection and safety requirements.

3.6 Initial Unit Startup Procedure

Outlines the procedure for starting the unit after installation.

USAGE AND OPERATION

4.2 Wire Controller Operation

Details unit on/off, mode selection, and temperature setting.

4.2.4 Setting Target Temperature

Details how to set the target temperature using the controller.

MAINTENANCE AND INSPECTION

5.2 Troubleshooting Guide

Lists common malfunctions, reasons, and solutions.

Distinction PASRW040 Specifications

General IconGeneral
ModelPASRW040
CategoryHeat Pump
SEER Rating16 SEER
Phase1
Maximum Operating Ambient Temperature (Cooling)115°F
Cooling Capacity40000 BTU
Heating Capacity42000 BTU
HSPF Rating9.0 HSPF
Refrigerant TypeR410A
Voltage208/230V