505-12 Power Supply
Description
The DMP 505-12 Series Power Supplies are regulated, power limited, switching power supplies. The 505 Series are
rated for 12VDC @ 5 Amps maximum. Each power supply includes a transformer, battery leads and is mounted in an
enclosure. Each power supply provides connections for AC input, DC output, and a standby battery. Also included
are a low AC input LED indicator, a low standby battery LED indicator, AC trouble and battery trouble relays, and
on-board transient protection for the AC input and the DC output. The 505-12LX includes two Model 867 Style W
Notication Modules.
Mounting the Enclosure
Mount the power supply metal enclosure in a secure, dry location to protect the unit from damage due to tampering
or the elements. It is not necessary to remove the PC board or transformer when installing the enclosure.
Mounting Optional NAC Modules
The power supply enclosure can accommodate the addition of two NAC modules for powering various listed
notication appliances. Use either the DMP Model 865 conventional Class A NAC module, the Model 866 conventional
Class B NAC module, or the Model 867 LX-Bus NAC module. Install any of the modules inside the enclosure using the
three hole mounting conguration. Plastic standoffs are provided with each module that attach to the enclosure.
See Figures 1 and 2.
J6
+ DC —
AC
Trouble
Batt
Trouble
To Earth
Ground
Input 120VAC 60 Hz
Unswitched
1.5 Amps
J4
J3J2
Green
LED
AC
Green
White
Black
NAC Module
NAC
Module
AC
+ BAT
Violet
Red
LED
DC
RED BLK
Battery Wires
(included)
AC and battery
output relay
connections
Connect J4 to a control
panel trouble zone or an
867 NAC Module trouble
zone.
Tie Down Wires
Shaded area for approximately two batteries.
To control panel
tamper zone.
Factory
Installed
12VDC @ 5 Amps
16VAC @ 100VA
Power Limited/class 2 wire routing
through knockouts into conduit.
Battery
Start
Ground
wire
attached
to the
inside of
the
enclosure.
N/C
C
C
N/C
Gray
For Access Control Applications
(UL 294) install the Model 307,
307-S, or 3012 Tamper Switch.
To Panel
Optional
wiring
to Panel
Connect NAC modules together.
Figure 1: 505-12, 505-12LX Wiring Diagram
Enclosure 505-12/505-12LX
Material 20-gauge, cold-rolled steel
Colors Gray (G) or Red (R)
Dimensions 15.75” H x 12.5” W x 4.75” D
Enclosure 505-12L
Material 18-gauge, cold-rolled steel
Colors Gray (G) or Red (R)
Dimensions 17.5” W x 13.5” H x 3.5” D
Enclosure 505-12A
Material 18-gauge with 16-gauge door
Colors Gray (G)
Dimensions 17.5” W x 13.5” H x 3.75” D
INSTALLATION GUIDE
Question and Answer IconNeed help?

Do you have a question about the DMP Electronics DMP 505-12 and is the answer not in the manual?

DMP Electronics DMP 505-12 Specifications

General IconGeneral
BrandDMP Electronics
ModelDMP 505-12
CategoryPower Supply
LanguageEnglish

Summary

505-12 Power Supply Description

Enclosure Mounting and Options

Mounting the Enclosure

Details on mounting the power supply metal enclosure securely in a dry location.

Mounting Optional NAC Modules

Information on adding NAC modules for notification appliances within the enclosure.

Wiring and Connections

AC Connection

Connects the transformer to an unswitched 120VAC 60 Hz power source.

Battery Connection

Connects the black and red battery leads to the negative and positive terminals.

AC and Battery Trouble Relay Connections

Connects supervisory relay outputs (NC, C) to a control panel or NAC zone.

DC Output

Connects devices requiring power to output terminals marked – DC +.

Operational and Compliance Information

Standby Battery Power Calculations

Calculates total Amp-hours required for standby battery backup.

NAC Module Connections

Referencing panel guide for connecting various NAC modules to power supplies.

FCC Information

Details equipment compliance with FCC Part 15 for digital devices.

Compliance Listing Specifications

Lists UL, ANSI, and other compliance standards for signaling and alarm systems.

NAC Modules Compatibility

Lists compatible NAC modules and horns like Wheelock MT-12/24.

Power Limited

States that circuits comply with inherent power limitation, Class 2 except red wire.

Specifications

Provides technical details on voltage, current, enclosure, and certifications.

Certifications

Lists various certifications like CSFM, FCC, NFPA, UL 1481, 603, 294.

Compatibility

Lists compatibility with all DMP Control Panels.