714/715 Installation Guide | Digital Monitoring Products 1
GET STARTED
714 and 715 zone expander modules allow you to increase the number of reporting zones available on DMP panels.
The modules connect to the panel Keypad Bus or LX‑Bus and are set to an address that determines the reporting
zone number.
The 714 provides four 5VDC Class B zones for use with burglary and non‑powered fire devices.
The 715 provides four 12VDC Class B zones for use with burglary, non‑powered, or powered fire devices.
What’s Included
One 714 Zone Expansion Module or One 715 Zone Expansion Module
(714) Four 1K Ohm Resistors
(715) Four 3.3K Resistors
12‑Wire Harness
Hardware Pack
INSTALLATION
1
Program the Panel
Program the zones on 714 or 715 zone expander modules with any of the panel’s burglary or fire zone types.
You can also program zones as an Arming zone type when they are being used with key switches. For more
information, refer to the appropriate panel programming guide.
2
Mount the Module
The714/715comes in a high‑impact plastic housing that you
can mount directly to a wall, backboard, or other flat surface.
For easy installation, the housing base contains holes that allow
you to mount themodule on a single‑gang switch box or ring.
1. Remove the housing fastener screws and separate the
top housing from the base.
2. Insert screws through the desired mounting holes on
the housing base. Refer to Figure 1 for mounting hole
locations.
3. Tighten the screws into place.
4. After wiring and addressing the module, attach the
housing top to the mounted base with the housing
fastener screws. Refer to Figure 2.
Mounting
holes
Housing Base
Housing
fastener
hole
Housing
fastener
hole
Figure 1: Mounting Hole Locations
Figure 2: Screw Locations