Solar Pump Inverter Chapter 4 Function Parameters
27
Chapter 4 Function Parameters
4.1 The Basic Function Parameters
The symbols in the function code table are described as follows:
"
" means the value of this parameter can be modified in stop and running status of drive;
"" means the value of this parameter cannot be modified when drive is running;
"
" means this parameter is a measured value that cannot be modified;
Default: The value when restored to factory default. Neither measured parameter value nor
recorded value will be restored.
Setting Range: the scope of setting and display of parameters.
Code Name Description
Factory
Default
Attri
bute
F00 Group: Basic function
F00.01
Command Source
Selection of
Run/Start
0Operation PanelLED off
1Terminal PanelL/R on
2Computer CommunicationsL/R
flash
1
F00.03 Maximum frequency F00.04600.00Hz 50.00Hz
F00.04
Upper frequency limit
F00.05
F00.03
50.00Hz
F00.05 Lower frequency limit 0.00 HzF00.04 0.00Hz
F00.06 Frequency setting
0: keypad digital setting
1: analog AI1 setting
0
F00.11 Acceleration Time 0 0.0s~3600.0s Model Set
F00.12
Deceleration Time 0
0.0s~3600.0s
Model Set
F00.13 Run direction
0: positive
1: reverse
2: prohibit reverse
0
F00.14
Carrier frequency set
1.0~15.0kHz
Model Set
F00.17 Inverter type
0G type
1P type
0
F00.18 Restore parameters
0No action
1Restore factory setting
2
Clear fault records
0
F01 Group: Start and stop control
F01.01 Starting frequency 0.00~50.00Hz
0.50Hz
(CT112-4T)
20.00Hz
(CT112-2S)
0.00Hz
(CT112A)
F01.02
Hold time of starting
frequency
0.0~50.0s 0.0s