Solar Pump Inverter Chapter 4 Function Parameters
33
Code Name Description
Factory
Default
Attri
bute
F07.09
Rotating speed
display coefficient
0.1~999.9%
Mechanical speed=120*display
frequency×F07.09/Number of motor
pole pairs
100.0% ○
F07.10
Linear speed display
coefficient
0.1~999.9%
Linear speed=Mechanical
speed×F07.10
1.0% ○
F07.11
Rectification bridge
temperature
0~100.0℃ ●
F07.12
Converting module
temperature
0~100.0℃ ●
F07.13
Software version
1.00~655.35
●
F07.14
Accumulative running
time
0~65535h
●
F07.18
Inverter Rate Power
0.4~3000.0kW
●
F07.19 Inverter Rate Voltage 50~1200V ●
F07.20
Inverter Rate Current
0.1~6000.0A
●
F07.27 Now Fault Type 0:Not fault
1:Over-current when acceleration
(OC1)
2:Over-current when deceleration
(OC2)
3:Over-current when constant
speed running(OC3)
4:Over-voltage when acceleration
(OV1)
5:Over-voltage when deceleration
(OV2)
6:Over-voltage when constant
speed running(OV3)
7:DC bus Under-voltage(UV)
8:IGBT Ph-U fault(OUT1)
9:IGBT Ph-V fault(OUT2)
10:IGBT Ph-W fault(OUT3)
11:Motor overload(OL1)
12:Inverter overload(OL2)
13:overload alarm(OL3)
14:IGBT overheat(OH1)
15:Rectify overheat(OH2)
16:Input phase failure(SFI)
17: Output phase failure(SFO)
18:Brake unit fault(bCE)
19:Ground short-circuit fault (ETH)
20:Under load fault (LL)
21:Communication fault(E.485)
22:External fault(EF)
23:EEPROM fault(EEE)
24:Trial time reached(END)
●
F07.28
Latest Fault Type
●
F07.29
The Second Fault
Type
●
F07.30
The Third Fault Type
●
F07.31
The Fourth Fault
Type
●
F07.32
The Fifth Fault Type ●