Solar Pump Inverter Chapter 4 Function Parameters
36
Code Name Description
Factory
Attri
Tens place:
0: inverter keeps running after
over/under load alarm
1: inverter keeps running after
under-load alarm and stops after
over-load alarm
2: inverter keeps running after
over-load alarm and stops after
under-load alarm
3: inverter stops after over/under
load alarm
Hundreds place:
0: detecting all the way
1:detecting during constant running
F11.13
Fault output terminal
actuation selection
0x00~0x11
Ones place:
0: action when under-voltage fault
appears
1: no action when under-voltage
fault appears
Tens place:
0:action during automatic resetting
1:no action during when automatic
resetting
0x00 ○
F11.16
Automatic frequency
reduction selection of
0: invalid
1:valid
1 ○
F14.00 Local address
0 is the broadcast address, 1
~
1 ○
F14.01 Baud rate
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
5: 38400bps
6: 57600bps
4 ○
F14.02 Data check
0: no check (N, 8,1) for RTU
1: even check (E, 8,1) for RTU
2: odd check (O, 8,1) for RTU
3: no check (N, 8,2) for RTU
4: even check (E, 8,2) for RTU
5: odd check (O, 8,2) for RTU
1 ○
F14.03
~
5 ○
F14.04
timeout detection
0.0 (invalid), 0.1~100.0s 0.0S ○