- 3 -
R20150924
Parameter
Push for 3 sec.
ST 1 0.0
FX3D
OUT1
OUT2
Run Mode
Select Control Type #1
Control Deviation Value #1
ON Delay Time #1
Minimum OFF Time #1
Minimum ON Time #1
Select Deviation Type #1
T Y 1
D F 1
Select Control Type #2
Control Deviation Value #2
T Y 2
D F 2
D T 1
F T 1
N T 1
T P 1
Output #1 setup value
ST 2
0.0
Output #2 setup value
Push
for 5 sec.
Push
for 3 sec.
Menu move Setup value
Run Mode
Select Lock Function
Select Sensor Type
Max. Sensor Input Range
Min. Sensor Input Range
Display Unit
Decimal Point Display
L O C
I N
S H
S L
U N T
D P
Push
for 10 sec.
Push
for 3 sec.
Menu move Setup value
Temperature Setting Group Setting 1 Group Setting 2 Group
1) Min OFF Time : It doesn’t make it output within Min. OFF Time after output is OFF. During Min OFF Time, output lamp is turned on with output after it ickers every 1 second intervals.
2) Min ON Time : It is for avoiding frequent ON/OFF of control output and maintains ON condition in spite of OFF condition during Min ON Time after being turned on.
3) Select Deviation Type : It selects deviation type. e.g) Condition (Cooling, Setup value 10.0, Deviation 1.0)
In case of +deviation -> Operate at ON (11.0) / OFF (10.0) In case of ±deviation -> Operate at ON (10.5) / OFF (9.5)
Temperature Setting Group
(SEL Button Push for 3 Sec.)
No Menu Code Unit Step Min Max Default Custom Setup
4 0001 Output #1 setup value
ST1
°C 0.1
UL1 UH1
0.0
4 0002
Output #2 setup value
ST2
°C 0.1
UL2 UH2
0.0
Setting 1 Group
(PRG Button Push for 5 Sec.)
No Menu Code Unit Step Min Max Default Custom Setup
4 0003
Output
#1
Select Control Type
TY1 OFF
(0) : Display
C
(1) : Cooling mode
H
(2) : Heating mode
C
(1)
4 0004
Control Deviation Value
DF1
°C
0.1
0.1 999.9
1. 0
4 0005 ON Delay Time
DT1
Sec 1 0 999
1
4 0006 Minimum OFF Time(
1)
FT1
Sec 1 0 999
0
4 0007 Minimum ON Time(
2)
NT1
Sec 1 0 999
5
4 0008 Deviation Type(
3)
TP1 P
(0) : Deviation
PN
(1): ± Deviation
P
4 0009 Set Value Max.
UH1
°C 1
UL1 SH 10 0
4 0010 Set Value Min.
UL1
°C 1
SL UH1 -45
4 0 011
Output
#2
Select Control Type
TY2 OFF
(0) : Display
C
(1) : Cooling mode
H
(2) : Heating mode
C
(1)
4 0012 Control Deviation Value
DF2
°C 0.1 0.1 999.9
1. 0
4 0013 ON Delay Time
DT2
Sec 1 0 999
2
4 0014 Minimum OFF Time(
1)
FT2
Sec 1 0 999
0
4 0015 Minimum ON Time(
2)
NT2
Sec 1 0 999
5
4 0016 Deviation Type(
3)
TP2 P
(0) : Deviation
PN
(1): ± Deviation
P
4 0017 Set Value Max.
UH2
°C 1
UL2 SH 10 0
4 0018 Set Value Min.
UL2
°C 1
SL UH2 -45