Technical Specications
Power 100–240Vac, 50/60Hz
Current MAX 6 VA
Connection Screw Bolt Connector(1.5mm
2
Wire Use Possibility)
Output Relay Output 2 Point (250Vac / 5A)
Input Temp. Sensor Input 1 Point
Dimensions 78(W)mm X 35(H)mm X 78(D)mm
Operation Temperature: -10 ~ 50°C, Humidity: Below 90%RH
Storage Temperature: -20 ~ 60°C, Humidity: Below 90%RH
Ordering guide
FX3D-00 Basic Model
FX3D-A1 4~20mA Trans output model
FX3D-R4 RS485 Comm. model
FX3D-A1R4 4~20mA Trans output & RS485 Comm. model
※ Specifications are subject to change without prior notice.
Components Accessories
User’s Manual
Ø5
35
SUS PIPE SHRINK TUBE LEAD WIRE
Ø6
100
SUS PIPE SPRING PROTECT LEAD WIRE
DPR-TH01-ET : NTC 5 KΩ at 25 °C / -50~105 °C / ±0.3 °C at 25 °C
DPR-TH02-P6D100L : NTC 10 KΩ at 25 °C / -50~150 °C / ±1.5 °C at 25 °C
Cautions
1. This product may cause an electric shock in handling. Please do not attempt to open it with power turned on.
2. This product should be installed in a place xed secured by a rack or panel.
3.This product can be used under the following environmental condition.
Indoor
Pollution Degree 2
At an altitude of 2000m or below
4. Power input must be within the designated ranges.
5. To turn on or turn off power supply for this product, please the circuit breaker or switch of a standard product of IEC 60947-1 or IEC 60947-3 product and install it within a close distance allowing convenient operation by user.
6. Please be understood that if this product is dismantled or modied discretionary, after sales service will not be able to be provided.
7. An output wire to be used for this product should be inammable grade FV1 (V-1 grade or above), the thickness of the wire should be AWG No. 20 or above(0.50mm2).
8. In order to prevent it from an inductive noise, please maintain the high-voltage wire and power wire separated.
9. Please avoid installing the product in a place where a strong magnetism, noise, severe vibration and impact exist.
10. When extending the sensor wire, use a shield wire and do not extend it unnecessary long.
11. The sensor wire and signal wire should be away from the power and load wires using conduits separately installed.
12. Please avoid using the product near a device generating strong high frequency noise (high-frequency welding machine, high-frequency sewing machine, high-frequency radiotelegraph, high capacity SCR controller)
13. Product’s damages other than those decribed in the guarantee conditions provided by the manufacturer shall not be respoinsible by us.
14. If this unit is used to control machineries (Medical equipment, vehicle, train, airplane, combustion apparatus, entertainment, processing and transportation equipment, elevator and various safety device etc.) enabling to effect
on human or property, it is required to install fail-safe device.
The Aforementioned precautions must be observed, and if you fail to do so, it may cause a product’s breakdown.
The specications, dimensions, and etc. are subject to change for enhancement without a prior notice.
Digital Temp Controller
User's Manual
FX3D
- Heating/Cooling Output
- Independent Timer Output
- High/Low Limit Alarm
- Defrost Output
- Sensor Calibration
- Sensor Error Detection
- Automatic Output Cycle after Sensor Error
- Auto Save and Restoration of Parameter Values
- Minimum On/Off Duration Time
- Analog Signal Output(4-20mA)
- Communication via RS485 MODBUS
- Remote Control(FX3D to FX3D)
DOTECH INC. 6F, JOONGANG-ILBO B/D, 30, Dongsan-ro, Danwon-gu, Ansan-si, Gyeonggi-do, KOREA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DOTECH FX3D and is the answer not in the manual?

DOTECH FX3D Specifications

General IconGeneral
Control ModePID
Input TypeThermocouple, RTD
Output TypeRelay, SSR, Analog
DisplayLED
Power Supply100-240 VAC
Control AlgorithmPID
CommunicationRS485

Related product manuals