Progra m D escript i on s: 5.31 Installer’s Lockout

6. Remove AC power from the control
7. Reconnect all original wiring and power up the control.
127($&SRZHUPXVWEHXVHGWRSRZHUWKHSDQHO7KHSDQHO
ZLOOQRWGHIDXOWLIRQO\WKHEDWWHU\LVXVHG
To default the main control panel software and other modules,
perform the following:
1. Enter the Installers Programming mode.
2. Enter the appropriate programming section [XXX].
3. Enter the Installers Code.
4. Re-enter the appropriate programming section [XXX].
The panel will take a few seconds to perform the default.
When the keypad is again operational the default is complete.
127(,IXVLQJ,GHQWLILHG:LUHOHVV.H\V3&YRUODWHU
RQO\ ZKHQ WKH PDLQ SDQHO LV GHIDXOWHG DOO ZLUHOHVV NH\
DFFHVVFRGHVPXVWEHUHSURJUDPPHG5HIHUWR\RXU3&
Y,QVWDOODWLRQ0DQXDOIRUPRUHLQIRUPDWLRQ
Restore LINKS2X50 to Default Programming. . Section [993]
Restore PC5132 to Default Programming . . . . Section [996]
Restore PC5400 to Default Programming . . . . Section [997]
Restore Panel to Default Programming . . . . . . Section [999]
5.31 Installer’s Lockout
If ,QVWDOOHU¶V/RFNRXW is selected, a hardware default cannot
be performed. If a software default is performed, all program-
ming will restore to factory default.
If ,QVWDOOHUV /RFNRXW 'LVDEOH is selected, the panel will
restore all programming to factory defaults when a hardware
or software default is performed on the main control panel.
To enable or disable Installers Lockout, perform the following:
1. Enter the Installers Programming mode.
2. Enter the appropriate programming section: [990] or [991].
3. Enter the Installers Code.
4. Re-enter the appropriate programming section: [990] or
[991].
Installer Lockout Enable. . . . . . . . . . . . . . . . . . Section [990]
Installer Lockout Disable . . . . . . . . . . . . . . . . . Section [991]
5.32 Walk Test (Installer)
The ,QVWDOOHU:DON7HVW can be used to test the alarm state of
each zone of the panel. The walk test cannot be used to test
zone type [24].
Before beginning the walk test, ensure the following condi-
tions are met:
1. The panel is disarmed
2. The .H\SDG %ODQNLQJ option is disabled (section [016]:
[3])
3. The )LUH %HOO LV &RQWLQXRXV option is disabled (section
[014]: [8])
4. The 7UDQVPLVVLRQ 'HOD\ is disabled, if Transmission
Delay is not required (section [370])
127()LUH7URXEOHVDUHQRWVXSSRUWHGLQ:DON7HVW
7RSHUIRUPD:DON7HVW
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
When any zone is violated the panel will activate the Bell Out-
put for two seconds, log the event to the event buffer and
communicate the alarm to central station. Each zone should
be tested several times during the test. Check the event buffer
to ensure that all zones and FAP keys are functioning properly.
7RVWRSWKHWHVW
Step 1 - Enter Installer Programming
Step 2 - Enter Section [901]
Check the event buffer after the Walk Test is complete, to
ensure that the Audible/Silent 24-hr PGM alarms have been
restored.
127(7KH$ODUP0HPRU\LVFOHDUHGXSRQHQWHULQJ:DON7HVW
PRGH :KHQ WKH :DON 7HVW LV FRPSOHWH WKH $ODUP 0HPRU\
OLJKWZLOOUHPDLQOLWEXWWKHUHZLOOEHQRDODUPVLQPHPRU\7KH
OLJKWZLOOWXUQRIIWKHQH[WWLPHWKHSDQHOLVDUPHG
Installer Walk Test Enable/Disable . . . . . . . . . . . Section [901]