EasyManuals Logo

Dynisco ATC770-0-2-3 User Manual

Dynisco ATC770-0-2-3
88 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
68
Default value: nan.
FILTER FOR DISPLAY AND CONTROLLER - Group 2
Available: Always.
Upper display: Time constant for the sixth order filter acting on the display and on the controller.
This filter is intended to remove the noise from input signal.
Lower display: AT.FL
Range: OFF, 0.5, 1, 2, 4, 8, 16 sec.
Default value: 1 sec.
AUTOMATIC STAND-BY - Group 2
Available: Always
Upper display: Status of Automatic Stand-by function
Lower display: ASB
Range: On (function enabled/OFF (function disabled)
Default value: OFF
AUTOMATIC STAND-BY PRESSURE LOW LIMIT - Group 2
Available: Only if ASB is equal to On.
Upper display: Pressure low limit threshold in percentage of full scale value.
Lower display: ASB.PL
Range: From 0 to 15% of full scale value.
Default value: 5%
AUTOMATIC STAND-BY RECOVERY TIME - Group 2
Available: Only if ASB is equal to On.
Upper display: Recovery time in seconds
Lower display: ASB.RT
Range: From 0 to 60 the OFF. OFF means that no recovery time is applied, that is the
frozen output value is held indefinitely.
Default value: OFF
LOCAL/REMOTE SET POINT SELECTION - Group 2
Available: Only if RI.TYP is different than OFF.
Upper display: Status of local/remote set point selection.
Lower display: LR.SP
Range: LOC/rEn. The selection is stored in nonvolatile memory; at power-on the last
selection is restored.
Default value: LOC.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dynisco ATC770-0-2-3 and is the answer not in the manual?

Dynisco ATC770-0-2-3 Specifications

General IconGeneral
BrandDynisco
ModelATC770-0-2-3
CategoryController
LanguageEnglish

Related product manuals