EasyManua.ls Logo

EASCO FST Series - Section 1: General; 1.1 Introduction; 1.2 Specification Requirements & Approvals

Default Icon
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Easco Boiler Corp 1175 Leggett Ave Bronx, NY 1047 T: 718.378.3000 F: 718.378.4560 info@easco.com easco.com
Page 9 of 46
SECTION 1: GENERAL
1.1 Introduction
EASCO Series FST, ESP, SM4 Scotch-Marine, Series SM5 Modified-Scotch-Marine,
Series PLW Firebox and Series FPS Scotch-Marine boilers are 3-Pass and 4-Pass
(only Series FPS), respectively, Water-backed Steel, Horizontal Firetube boilers
built in accordance with ASME B&PV Code Section IV Rules for The Construction
of Heating Boilers. Specifically designed for forced draft firing utilizing fuel burning
equipment capable of firing commercial standard light and heavy fuel oils, natural
gas, or combination gas/oil fuel burning apparatus, these Boilers are available for low
pressure steam (LPS 15 PSIG MAWP) and hot water (HW 160 PSIG MAWP / 250 °F
MAWT) applications providing thermal or combustion efficiencies that meet, or exceed,
the minimum efficiency criteria and requirements of ASHRAE Standard 90.1 Energy
Standard for Buildings Except Low-Rise Residential Buildings (I-P Edition).
This Manual provides the required information necessary to successfully and properly
install, commission, operate, maintain and service the Boiler Equipment.
1.2 Specification Requirements and Approvals
EASCO Packaged Boiler Assemblies (PBA) are available to meet with any specific
requirement and applicable standard such as ASME CSD-1, Factory Mutual (FM),
Industrial Risk Insurers (IRI), Underwriters Laboratories (UL) and specific Federal, State,
Local Municipality, Local Jurisdictional Authority and/or Utility requirements, Codes and
Standards.
As indicated above, all EASCO products, covered by this Manual, are manufactured
in accordance with ASME B&PV Code Section IV. All vessels are inspected by an
independent, third party, Authorized Inspector (AI), commissioned by The National
Board of Boiler and Pressure Vessel Inspectors (NBBPVI). The AI is an employee of an
Independent Authorized Inspection Agency, an insurance company who underwrites
EASCO’s insurance policy.

Table of Contents