Connectivity
WiFi 2.4 GHz b/g/n connection
Easee Link RF
TM
Control charging via Easee App
RFID/NFC reader
OCPP 1.6 via Easee API
Bluetooth BLE 4.2
Protection
Integrated overload protection according to EN IEC 61851-1:2019
Built-in ground fault protection (30 mA AC/6 mA DC)
External approved Type-A RCD (1 phase: 2P; 3 phase 3P+N; max 40 A) is required
Degree of protection IP54 (the backplate is IP22 without cover)
Impact resistance IK10
Insulation class I
Overvoltage category III
Installation
Installation network TN, IT or TT (detected automatically)
Installation circuit breaker Max 40 A
Short circuit current limited to 10 kA
Wire cross-section Copper wire, between 2.5 and 16 mm
2
:
1 phase 32 A: 4.0 mm
2
to 16mm
2
3 phase 16 A: 2.5 mm
2
to 16mm
2
Protective earth: minimum 4 mm
2
Use the largest possible wire cross-section to make the site future-proof
Cable diameter 8–22 mm
Terminal torque 5 Nm
Cable strip length 12 mm
Notes
Charging station is mode 3 equipment