MODEL EA906II EA9010II EA9015II EA9020II
Capacity 6KVA/5.4KW 10KVA/9KW 15KVA/13.5KW 20KVA/18KW
INPUT
Rated Voltage
3/1: 360V/365V/380V/400V/415VAC;
1/1: 208V/210V/220V/230V/240VAC.
(Set up by LCD display)
Voltage Range
3/1: Half load (190-520)±5VAC, Full load (277-520)±5VAC;
1/1: Half load (110-300)±5VAC, Full load (160-300)±5VAC.
Frequency 40-70Hz±0.5% (Auto sensing)
Power Factor
3/1: ≥0.95;
1/1: ≥0.99.
BYPASS
Voltage Range 160V-Rated output voltage+32V
Frequency 50/60Hz±5Hz
OUTPUT
Voltage 208V/210V/220V/230V/240Vac Setting available via LCD
Voltage Regulation ±1%
Frequency Synchronized with utility on AC mode; 50/60±0.1Hz on battery mode
Waveform Pure sine wave
Crest Factor 3:1
Harmonic Distortion ≤2%(Linear load); ≤5%(Non-linear load)
Transfer Time
AC mode to battery mode: 0ms
Inverter mode to bypass mode: 0ms
Overload Capability
105%-125%: Transfer to bypass after 3mins;
125%-150%: Transfer to bypass after 30s;
>150%: Transfer to bypass after 100ms
EFFICIENCY
AC Mode ≥93%
Battery Mode ≥92%
ECO Mode ≥98%
BATTERY
DC Voltage 192V/240VDC
Inbuilt Battery of Standard
Model
16*7AH 16*9AH NO
Charge
Current
Standard Model 1A
Long Time Model 7A
Typical Recharge Time 8 hours recover to 90% capacity
ALARM
Utility Failure Beep/4s
Battery Low Beep/1s
Overload Beep Twice/1s
UPS Fault Long Beep
ENVIRONMENT
Humidity 20~90% RH @ 0~40(non-condensing)
Noise Level ≤58dB (1m) ≤60dB (1m)