3
200 A 15/25 kV class elbow installation instructions
InstallatIon InstructIons   MN650042EN   February 2017
Preparation of concentric neutral cable
Step 1
Measure down from top of the cable a minimum of 8 1/2”.
Remove cable jacket (if jacketed cable is used) to expose 
neutral wires.
Unwind neutral wires.
ote:N If an Eaton Cooper Power series jacket seal is used, 
follow instructions supplied with the jacket seal kit.
Step 2
Measure down from top of the cable 5 3/4”.
Remove the insulation shield. Take care not to nick or  
gouge insulation.
Step 3
Measure down from the top of the cable 1 15/16”.
Remove the insulation and conductor shield to expose the 
bare conductor. Take care not to nick the conductor.
Place a 1/8” bevel on the insulation to ease installation.
Step 4
If not already in place, apply a suitable jacket seal over the 
jacket and exposed neutral wires.
Proceed to Step 5.
First
crimp
placed
below
knurl
Clean
and
lubricate
Clean
excess
inhibitor
grease
Step 5 Step 6 Step 7
Clean and 
lubricate cable 
entrance
Clean and 
lubricate 
Attach 
ground lead 
to elbow 
ground tab
Attach lead 
to system 
ground