EasyManuals Logo

Eaton 600 A 15 kV class push-OP Assembly/Installation Instructions

Eaton 600 A 15 kV class push-OP
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Catalog data MN650002EN
Effective February 2019
Deadbreak apparatus connectors
Step 2.
Remove concentric neutral wires or jacket
ote:N Care should be taken to not cut or score the
neutral conductors when cutting the cable jacket.
Measure 13" (330 mm) from end of cable.
Refer to Figure 15.
For jacketed neutral cable, remove jacket to
13" dimension.
For unjacketed neutral cable, bind neutral wires using
three (3) wraps of tape at 13" dimension.
Pull back concentric neutral wires. Allow enough extra
concentric neutral wires to connect to ground after installation
and allow movement to insulated standoff bushing.
Step 3.
Remove insulation shield
Remove insulation shield 10 1/2" (267 mm) from end of
cable. Refer to Figure 16.
Do not cut or nick insulation.
Step 4.
Put tape marker in place
Measure 1" (25 mm) from end of insulation shield.
(Refer to Figure 16.)
Wrap two turns of tape to serve as marker for cable
adapter location.
Step 5.
Remove conductor insulation
ote:N Do not pencil cable.
Remove insulation exposing bare conductor to length of
4 1/2" (114 mm). Refer to Figure 17.
ote:N Do not unwind conductor strands.
Step 6.
Bevel insulation
Remove sharp edge of insulation by beveling at a 45°
angle for approximately 1/4" (6 mm). (Refer to Figure 18.)
Figure 15. Line illustration of removing concentric
neutral wires.
Bushing
Cable
1 3/4" ± 1/4"
(44 mm ± 6 mm)
13" ± 1/4"
(330 mm ± 6 mm)
Concentric neutral
wires
Figure 16. Line illustration of cable stripback.
10 1/2" ± 1/8"
(267 mm ± 3 mm)
1"
(25 mm)
Tape marker Insulation shield
Insulation
Figure 17. Line illustration of bare conductor length.
4 1/2" ± 1/8"
(114 mm ± 3 mm)
Tape marker
Bare conductor
Insulation
Figure 18. Line illustration of insulation bevel.
Bevel
Insulation
1/4"
(6 mm)
9
600 A 35 kV class BOL-T connector assembly installation instructions MN650002EN February 2019

Other manuals for Eaton 600 A 15 kV class push-OP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton 600 A 15 kV class push-OP and is the answer not in the manual?

Eaton 600 A 15 kV class push-OP Specifications

General IconGeneral
BrandEaton
Model600 A 15 kV class push-OP
CategoryCables and connectors
LanguageEnglish

Related product manuals