16. Close and secure the CL-7 control panel using the self-
adjusting latch.
1 7. Review the General Electric nameplate to determine
correct overall Potential Transformer (PT) ratio entered
at FC 44 on control.
18. Complete the control programming and testing as
required. Refer to document MN225003EN, CL-7
Control Installation, Operation, and Maintenance
Instructions for proper control configuration and start
up procedures.
IMPORTANT
If the neutral light does not illuminate when the regulator
is in neutral, try flipping the neutral light switch to the
opposite position. See Figure 14.
15
CL-7 Control Panel Retrofit
InstallatIon InstructIons MN225018EN April 2018