Figure 1. Line drawing showing 15 kV 600 A PUSH-OP bushing adapter cap.
LATCH HANDLE
PUSH PLATE
200 A INTERFACE
OPERATING EYE
LOCKING SLOT
SHROUD PIN
BAIL BRACKET
LOCKING TEETH
FIRST NOTCHES
Product Information
Introduction
Eaton's Cooper Power™ series 600 A, 15, 25, and 35 kV
PUSH-OP™ bushing adapter cap is a factory assembled
load reducing tap plug (LRTP) and bushing extender unit.
It is used to convert a 600 A deadbreak interface to a
200 A loadbreak interface* allowing for safe testing and
grounding. It has electrical characteristics identical to those
of the LRTP. Used with Eaton's Cooper Power series 200A
insulated protective cap, M.O.V.E. arrester, grounding
elbow or loadbreak elbow connector, a bushing adapter
provides a fully shielded, submersible unit that meets the
requirements of IEEE Std 386™-2006 standard.
* Switching rating limited to single-phase 21.1 kV.
WARNING
The 600 A 15, 25 and 35 kV PUSH-OP bushing adapter
cap is designed to be operated in accordance with
normal safe operating procedures. These instructions are
not intended to supersede or replace existing safety and
operating procedures. Terminators must be de-energized
during operation or maintenance. Visible break and
adequate grounding must be provided before cable
work proceeds. (Ensure that the component is rated for
the intended application before it is installed.)
The bushing adapter cap should be installed and
serviced only by personnel familiar with good safety
practice and the handling of high-voltage electrical
equipment. Failure to comply may result in death,
severe personal injury or equipment damage.
WARNING
All associated apparatus must be de-energized during
installation and/or maintenance. Failure to comply may
result in death, severe personal injury or equipment
damage.
1600 A 15, 25, AND 35 KV CLASS PUSH-OP BUSHING ADAPTER CAP INSTALLATION INSTRUCTIONS MN650050EN May 2017