Compression connector installation procedures
Equipment provided
BT-TAP Connector Assembly Kit includes:
T-body
Cable Adapter
Compression Connector with 11/16” unthreaded spade
BT-TAP Loadbreak Reducing Tap Plug (BLRTP)
Extended Length Stud
200 A Loadbreak Protective Cap (when furnished)
Silicone Lubricant
Instruction Sheets
Tools Required
5/16” Hex Shaft (Catalog Number HD635)
Cable Stripping Tools
Torque Wrench
5 mm or 8 mm Allen Wrench
Prepare the cable
Step 1.
Train Cable
Position cable vertically so that it is centered between
apparatus bushing and parking pocket, parallel to, and 7"
(178 mm) from apparatus frontplate.
Provide adequate cable slack for cable movement
between standoff bushing and apparatus bushing.
Support cable as needed to maintain position.
Cut cable 1.75" (44 mm) from centerline of bushing. Refer
to Fig ure 14.
Figure 14. Line illustration for cable training.
Bushing
Cable
1.75" ± .25"
(44 mm ± 6 mm)
7"
(178 mm)
Table 3. Conductor Size and Type
Compression Connector
Concentric or
Compressed Compact or Solid
Compression
Conductor Code
AWG or
kcmil mm
2
AWG or
kcmil mm
2
No Connector 00
#2 35 1 - 11
#1 - 1/0 50 12
1/0 50 2/0 70 13
2/0 70 3/0 - 14
3/0 - 4/0 95 15
4/0 95 250 120 16
250 120 300 - 17
300 - 350 - 18
350 - 400 185 19
400 185 450 - 20
450 - 500 240 21
500 240 600 300 22
600 300 700 - 23
650 - 750 - 24
750 - 900 - 25
900 - 1000 500 26
1000 500 - - 27
1250 630 - - 28
- - - - -
- - - - -
8
600 A 35 kV class BT-TAP connector system installation instructions for MN650003EN February 2015