Step 17
Ground system
Connect tie-off tabs of BLRTP and T-body with a strand of
drain wire to cable concentric neutral wires to common
ground point. (Refer to Figure 30.)
Connect 200 A product (i.e., Protective Cap, Grounding
Elbow, M.O.V.E. Arrester) drain wire to common ground.
Connect concentric neutral wires to common ground
point leaving adequate slack for hotstick operation.
Seal off jacket as required. (Tape sealing compound or
shrink tubing.)
Figure 30. Line illustration of grounding.
Concentric Neutral
Wires
T-body
Drain Wire
14
600 A 35 kV class BT-TAP connector system installation instructions for MN650003EN February 2015