Step 17
Ground system
•
Connect tie-off tabs of BLRTP and T-body with a strand of
drain wire to cable concentric neutral wires to common
ground point. (Refer to Figure 30.)
•
Connect 200 A product (i.e., Protective Cap, Grounding
Elbow, M.O.V.E. Arrester) drain wire to common ground.
•
Connect concentric neutral wires to common ground
point leaving adequate slack for hotstick operation.
•
Seal off jacket as required. (Tape sealing compound or
shrink tubing.)
Figure 30. Line illustration of grounding.
Concentric Neutral
Wires
T-body
Drain Wire
14
600 A 35 kV class BT-TAP connector system installation instructions for MN650003EN February 2015