600 Ampere Deadbreak Junction 15 & 25 kV and 35 kV Class
InstallatIon InstructIons MN650044EN May 2017
Procedure
Deadbreak junction assembly kit
Deadbreak Junction
Lubricant
Instruction sheet
Figure 1. Assembly kit
WARNING
All associated apparatus must be de-energized during
installation or maintenance.
CAUTION
The 600 Ampere Deadbreak Junction is designed to
be operated in accordance with normal safe operating
procedures. These instructions are not intended to
supersede or replace existing safety and operation
procedures.
The junction should be installed and serviced only by
personnel familiar with good safety practices and the
handling of high-voltage electrical equipment.
ote:N For product applications that require ratings or
characteristics not shown in current publications,
contact Eaton for specific recommendations.
Install
1. Mount the deadbreak junction solidly. The following
tables provide mounting dimensions for an Eaton-
supplied bracket. User-supplied mountings should be
designed to prevent excessive stress while holding the
junction firmly.
2. Connect the junction bracket to the system ground.
(Be sure that the junction’s exernal conducting shield
surface is connected to the system ground.)
Clean and lubricate
1. Remove the protective shipping caps.
2. Clean and lubricate the interfaces of the deadbreak
junction and mating apparatus.
3. Use lubricant (supplied) or Eaton-approved equivalent.
Assemble
1. Install the cleaned and lubricated mating apparatus per
instructions provided with the product.
2. All interfaces must be covered with the mating
apparatus.