UPS OPERATING INSTRUCTIONS
Eaton 9395 UPS (225–275 kVA) Installation and Operation Manual S 164201683 Rev 3 www.eaton.com/powerquality
7-11
Table 7‐5. Command Menu Operation
Function Subfunction Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass
mode.
Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to Disable when the
Energy Saver System mode is enabled.
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Start High Alert Starts High Alert mode.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Load Off Displays the Load Off screen (see paragraph 7.2.7).
Bypass
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command or proceed to further
command screens.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from Online
mode.
Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from Bypass
mode.
Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to Disable when the
Energy Saver System mode is enabled.
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode. Enable changes
to Disable when the Variable Module Management System mode is enabled.
Start High Alert Starts High Alert mode.
Load Off Displays the Load Off screen (see paragraph 7.2.7).
Charger Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function desired,
then press the SELECT pushbutton to execute the command.
UPM On Turns the UPM on without transferring the load to Online mode. The Load is on
bypass.
UPM Off Transfers the load to bypass and turns the UPM off.
UPM Go to Online Turns the UPM on and transfers the load to Online mode.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the factory or by an Eaton
Customer Service Engineer.