UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (225–275 kVA) Installation and Operation Manual S 164201683 Rev 3 www.eaton.com/powerquality
3-7
S The UPS cabinet is shipped with a debris shield covering the ventilation grill on top
of the unit. Do not remove the debris shield until installation is complete. However,
remove the shield before operating the UPS. Once the debris shield is removed, do
not place objects on the ventilation grill.
S In a common battery system, single and multiple UPMs are powered from one
common battery source. In a separate battery system, multiple UPMs are each
powered from separate battery sources.
S UPMs in distributed bypass and parallel systems must use a separate battery
system.
S On a UPS configured for separate rectifier inputs, all sources that feed the separate
rectifier inputs must be derived from a common ground point.
S A Field Installed UPM (FI-UPM) is always designated as UPM 4.
If the power rating listed on the nameplate of the installed UPS is not found in the
following tables, wire the UPS using the fully rated specifications. Otherwise,
calculate the required wire, conduit, and breaker sizes using the following guidelines
in addition to those already listed in paragraph 3.2.2:
S Select wire size according to the UPS nameplate.
S Do not use wire larger than the largest size listed in Table 3‐4 through Table 3‐6.
S Use terminal recommendations from Table 3‐7 through Table 3‐10.
S Size and number of conduits must not exceed those listed in Table 3‐11.
S Select overcurrent protection input, battery, and output breakers according to the
UPS nameplate rated for either 80% or 100%.
S Follow all applicable NEC and local codes.