5.Technical data
UPS MODELS
9E6Ki
220 - 230 - 240 220 - 230 – 240 / 380 – 400 - 415
Maximum operating voltage [Vac]
276 276 / 478
Nominal frequency [Hz]
50 - 60
Nominal current [A]
Recharge time (standard versions)
< 8h for 90% of the charge
Expandability and nominal
voltage of the Battery Box
180Vdc 240Vdc 240 + 240Vdc 240 + 240Vdc
Charging current
(for XL versions only)
Not applicable 4,4A 5A 5A
Selectable: 220/230/240
Frequency [Hz]
Selectable: 50, 60 or auto sensing
Nominal power [VA]
6000 10000 15000 20000
Nominal power [W]
4800 8000 12000 16000
Overload: 105% < load < 110%
Bypass line available: activates the bypass after 5 min, then
continues to work
Bypass line not available: locks after 5 min
Overload: 110% < load < 130%
Bypass line available: activates the bypass after 1 min, then
locks after 1 min
Bypass line not available: locks after 1 min
Overload: 130% < load < 150%
Bypass line available: activates the bypass after 10 s, then
locks after 10 s
Bypass line not available: locks after 10 s
Overload load > 150%
Bypass line available: activates the bypass after 100 ms, then
locks after 1 s
Bypass line not available: locks after 1 s
Leakage current to earth [mA]
< 8mA
Ambient temperature [°C]
0 – 40
Humidity < 95% without condensation
Protection devices
Batteries deep discharge - overcurrent - short circuit - overvoltage -
undervoltage - circuit breaker
Dimensions W x D x H [mm]
262 x 613x 709 350 x 706 x 818
Weight [kg]
Operating Temperature 0
o
C to 40
o
C
Operating humidity 0-95% no condensing
Altitude Up to 1,000 meters above sea level with 10% derating per 1000m
Storage temperature
-15
o
C to 60
o
C without batteries
0~35°C with batteries
Nominal battery voltage [Vdc]
180Vdc 240Vdc
Dimensions W x D x H [mm]
262 x 580 x 709
Weight [kg]