Table 3. Interrupting ratings
Recloser
type
Trip-coil
continuous
current (amps)
Minimum-
trip current
(amps)
Interrupting current
(rms symmetrical amps)
E
@24.9 kV
5 10 300
10 20 600
15 30 900
25 50 1500
35 70 2100
50 100 2500
70 140 2500
100 200 2500
4E
50 100 3000
70 140 4000
100 200 4000
140 280 4000
200 400 4000
280 560 4000
V4E
15 30 900
25 50 1500
35 70 2100
50 100 3000
70 140 4200
100 200 6000
140 280 6000
170 340 6000
200 400 6000
280 560 6000
H
@2.4 through 14.4 kV
5 10 125
10 20 250
15 30 375
25 50 625
35 70 875
50 100 1250
4H
@4.8 @8.32 @14.4
5 10 200 200 200
10 20 400 400 400
15 30 600 600 600
25 50 1000 1000 1000
35 70 1400 1400 1400
50 100 2000 2000 2000
70 140 2800 2500 2000
100 200 3000 2500 2000
V4H
5 10 200 200 200
10 20 400 400 400
15 30 600 600 600
25 50 1000 1000 1000
35 70 1400 1400 1400
50 100 2000 2000 2000
70 140 2800 2500 2000
100 200 3000 2500 2000
140 280 3000 2500 2000
200 400 3000 2500 2000
Recloser
type
Trip-coil
continuous
current (amps)
Minimum-
trip current
(amps)
Interrupting current
(rms symmetrical amps)
L
@4.8 @8.32 @14.4
25 50 1500 1500 1500
35 70 2100 2100 2100
50 100 3000 3000 3000
70 140 4200 4200 4000
100 200 6000 5000 4000
140 280 6000 5000 4000
200 400 6000 5000 4000
280 560 6000 5000 4000
V4L
@2.4 through 14.4 kV
15 30 900
25 50 1500
35 70 2100
50 100 3000
70 140 4200
100 200 6000
140 280 6000
170 340 6000
200 400 6000
280 560 6000
5
Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions
OPERATION INSTRUCTIONS MN280051EN May 2017