Ratings and specifications
Table 1. Ratings and specifications
Recloser type
Rated system
nominal
voltage (kV)
Rated system
max. voltage (kV)
Rated system
withstand voltage
(BIL) (kV)
60 Hz Insulation level
withstand rating
Continuous
current (amps)Dry 1-Min. (kV) Wet 10-Sec (kV)
E 24.9 27 150 60 50 100
4E 24.9 27 150 60 50 280
V4E 24.9 27 150 60 50 280
H 14.4 15.0 95 35 30 50
4H 14.4 15.5 110 50 45 100
V4H 14.4 15.5 110 50 45 200
L 14.4 15.5 110 50 45 280
V4L 14.4 15.5 110 50 45 280
Table 2. Rated interruptions
Recloser type % Interrupting rating Maximum circuit X/R ratio Number unit operations Total unit operations
E
15-20 2 40
7245-55 5 20
90-100 12 12
4E
15-20 3 32
6445-55 6 20
90-100 13 12
V4E
15-20 3 96
24845-55 7 120
90-100 15 32
H
15-20 2 40
10045-55 4 40
90-100 8 20
4H
15-20 2 32
6845-55 5 24
90-100 10 12
V4H
15-20 2 128
27245-55 5 96
90-100 10 48
L
15-20 3 32
6445-55 6 20
90-100 12 12
V4L
15-20 3 96
24845-55 7 120
90-100 15 32
4
Types E, 4E, V4E, H, 4H, V4H, L, and V4L single-phase recloser installation and operation instructions
OPERATION INSTRUCTIONS MN280051EN May 2017