Type VSA12, VSA16 and VSA20/800 maintenance instructions
6MAINTENANCE INSTRUCTIONS   MN280064EN   October 2017
1.   If the recloser passes the closed contacts tests 
(Tests1 and 2) but fails the open-contacts test (Test 
3) a deteriorated vacuum in one or more of the 
interrupters is most likely the cause. Retest each 
vacuum interrupter individually to determine the failed 
phase or phases, and replace the interrupter(s). Retest 
to confirm the repair.
2.  If the recloser fails the closed-contacts tests  
(Tests 1and 2) the cause is likely to be a diminished 
electrical clearance or a failed insulation. After 
correcting the problem, retest to confirm the repair.
Shop maintenance instructions
The operations described in this section should be 
performed under the cleanest conditions possible. No 
special tools are required for any of the repair procedures.
Bushings
Bushing maintenance generally consists of a thorough 
cleaning and a careful examination for chips, cracks or 
other physical damage during the periodic maintenance 
inspection. Bushing porcelain must be replaced whenever 
damage is discovered. The porcelain can be replaced 
without removing the bushing assembly from the recloser.
To replace bushing porcelain proceed as follows, refer to 
Figure 7:
1.   Unscrew the bushing terminal, discard the  
terminal gasket.
Bushing 
terminal
Terminal 
gasket
Bushing 
porcelain
Roll pin
Bushing rod
Hex nuts
Bushing 
clamps
Split ring
Lower 
gasket
Figure 7.  Bushing porcelain replacement
2.  Remove the three hexnuts and bushing clamps that 
secure the bushing to the recloser housing.
3.  Remove and discard the lower bushing gasket.
4.  Twist off the split aluminum ring from the old bushing 
and install on the new bushing porcelain, if it is still in 
good condition; replace if damaged.
CAUTION 
Bushing damage. The split aluminum ring must be 
replaced if damaged. The clamping ring cushions and 
distributes the pressure between the bushing flange and 
the bushing. If bushing clamps are assembled without a 
new clamping ring, the bushing may be damaged when 
clamp hardware is tightened.  
T234.1
5.  Install a new lower bushing gasket and slide the new 
bushing porcelain, into the recloser housing, over the 
bushing rod. Make sure that the roll pin is seated in the 
locking groove in the top of the bushing.
6.  Position the clamping ring with the split centered 
between two clamp bolts.
7.   Install bushing clamp hardware and tighten nuts evenly, 
a little at a time, to 6-10 ft-lbs. torque.
 CAUTION 
Dielectric failure, bushing damage. To prevent gasket 
leaks or bushing damage, clamping force must be applied 
gradually and equally in rotation to each bolt. If the 
clamping force is not evenly applied, seal leakage can 
result, compromising the dielectric capabilities of the 
recloser and can cause possible personal injury. Unequal 
clamping force can cause bushing breakage.  
T235.2
8.  Apply a very small amount of petroleum jelly to the 
knurled inside surface of the bushing terminal.
9.  Install a new terminal gasket and the bushing terminal, 
tighten to 35 ft-lbs. torque.
Vacuum interrupters
Vacuum interrupters must be replaced when:
 
They lose their vacuum as evidenced by a failure during 
the low-frequency dielectric withstand test across the 
open contacts; or
 
The interrupter contacts have eroded beyond their useful 
life as evidenced by the position of the scribe mark on 
the moving contact rod.
To replace an interrupter refer to Figure 8, and proceed 
asfollows:
1.   Remove fused pullout switch to de-energize AC power 
source to operator mechanism.
2.  Make sure recloser contacts are open; manually 
operate mechanism until contact position indicator 
reads OPEN and closing spring status indicator reads 
SPRINGS DISCHARGED.
3.  Remove nylon hardware, or wire tie, securing insulating 
barrier to stringers, remove insulating barrier.
4.  Remove hardware and clamp that secure long bushing 
rod to lower interrupter support bracket.