Type VSA12, VSA16 and VSA20/800 maintenance instructions
3 MAINTENANCE INSTRUCTIONS   MN280064EN   October 2017
Table 5.  Current ratings
VSA-12 VSA-16 VSA-20
Continuous current rating (A) 800 800 800
Symmetric interrupting current (A) 12,000 16,000 20,000
Cable charging current (A) 2 2 2
Magnetizing current (A) 28 28 28
3 Second current, symmetric (A) 12,000 16,000 20,000
Momentary current, asymmetric (A) 20,000 25,600 32,000
Table 6.  Mechanical specifications
Operating temperature (°C)
Minimum -30
Maximum +50
Closing mechanism  Spring operated
Opening mechanism Spring operated
Contact gap (inches (mm)) 0.5 (13,7)
Close contact travel time (cycles (ms)) 0.5 (8)
Open contact travel time (cycles (ms)) 0.5 (8)
Maximum arcing time (cycles (ms))  1.0 (17)
Interrupting time (cycles (ms))  2.5 (42)
Allowable contact erosion (inches (mm)) 0.125 (3,2)
Opening time (24 vdc solenoid, signal to  
contact part) (ms)
 19-25
Closing time (24 vdc solenoid, signal to  
contact make) (ms)
32
Maintenance
Frequency of maintenance
Because reclosers are applied under widely varying operating 
and climactic conditions, maintenance intervals are best 
determined by the user, based on actual operating experience. 
To assure proper and trouble-free operation, reclosers must be 
maintained when they have operated the equivalent of a rated 
duty cycle (see Table 2). In the absence of specific operating 
experience the following procedures are recommended:
  When the type VSA recloser is operated under usual 
service conditions as defined in ANSI (American 
National Standards Institute) C37.60, “Standard 
Requirements for Overhead, Pad Mounted, Dry Vault 
and Submersible Automatic Circuit Reclosers and Fault 
Interrupters for AC Systems”, it is recommended that 
the following maintenance procedures be performed at 
the completion of an equivalent duty cycle.
ote:N ANSI C37.61, “Guide for the Application, Operation 
and Maintenance of Automatic Circuit Reclosers”, 
gives a procedure for converting the rated standard 
duty cycle into an equivalent duty cycle based on the 
actual operating duty of the recloser.
  However, if the recloser has not completed an equivalent 
duty cycle within THREE YEARS, it is recommended 
that an inspection be made at that time. (See Steps one 
through ten of “Periodic Maintenance Inspection.”)
Periodic maintenance inspection
Each maintenance inspection at the completion of an 
equivalent duty cycle should include at least the following:
1.   Bypass and remove the recloser from service: 
a.  Disconnect the control cable from the recloser.
b.  Remove the fused pullout switch to de-energize 
the 240 Vac power source to the operator 
mechanism.
2.  Visually inspect external components:
a.  Check for broken or cracked bushings; replace as 
necessary. (See “Shop Maintenance Instructions—
Bushings” for procedure.)
b.  Check for paint scratches and other mechanical 
damage; touch up to inhibit corrosion.
3.  Visually inspect the operator mechanism:
a.  Check interior of the operator mechanism cabinet 
for accumulation of dust and dirt; clean as 
necessary.
b.  Check door gasket for effectiveness of seal, repair 
or replace as required.
c.  Visually inspect all components for worn or broken 
parts and corrosion; replace as necessary.
d.  Check for broken or loose wiring terminals at the 
various components and terminal boards.
 CAUTION
Do not use excessive force when replacing brush holder 
caps; excessive tightening may crack the caps.
e.  Check the motor brushes for excessive wear and 
burning; replace as needed.
f.  Record counter reading in the record log.
4.  Close and trip the recloser manually several times to 
check mechanical operation. (See“Manual Operation— To 
Close the Recloser” for manual operating instructions.)
5.  Perform a dielectric withstand test to check the 
insulation level of the recloser and the vacuum integrity 
of the interrupters. (See “Insulation Level Withstand 
Tests” for procedure.)
6.  Remove cabinet side panels to expose the internal 
components.
7.   Check the contact erosion of the vacuum interrupters:
a.  Locate the scribe mark on the moving contact rod 
at the top of the interrupter. (See Figure 3.)