QD5 tap-changer reversing neutral stationary 
contact assembly kit number 5791646A26
(Refer to service Information MN225025EN)
General
The purpose of this replacement kit is to provide the parts 
and installation instructions for replacement of the reversing 
neutral stationary contact on a QD5 Quik Drive tap-changer
Parts supplied
Item Part Number Description Qty
1 0791646A26 Reversing Neutral Stationary 
Contact
1
Tools required
• 
Ratchet Wrench
• 
3/8 inch Socket
• 
7/16 inch Socket
• 
9/16 inch Deep-well Socket
• 
Torque Wrench, in-lbs
• 
Small flat-blade Screwdriver or 5/32 inch Allen Wrench
• 
8" Long flat-blade Screwdriver
• 
Loctite
®
  243™ Threadlocker
Installation procedure 
Removing existing contact assembly
ote:N Retain all hardware.
1.   Hold the reversing movable contact assembly to 
prevent it from moving. Using a 9/16" wrench, loosen 
and remove the reversing actuator arm nut. See Figure 
54.
2.  Lift outward on the reversing actuator arm and remove 
it from the reversing movable contact bushing. The 
reversing actuator shaft may be tapped in to allow 
clearance to remove the arm. See Figures 55 and 56.
Figure 53.  Reversing neutral stationary contact.
Figure 55. Reversing actuator arm removal.
Reversing 
Actuator 
Shaft
Reversing 
Actuator 
Arm
Figure 54. Reversing actuator arm nut removal.
Reversing Neutral 
Stationary Contact
Reversing 
Segment 
Actuator Arm
Reversing 
Movable Contact 
Assembly
Reversing Actuator 
Arm Nut
23
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS   MN225012EN   March 2016