Holding switch
Eaton's tap-changers are equipped with a holding switch 
to assure that a tap-changer operation is completed. This 
switch also provides a repetitive and accurate opening 
action causing the motor to stop the drive components 
with correct alignment. A signal from the holding switch 
activates the operations counter and prevents time delay 
reset during a tap change. The holding switch is operated by 
a pinion cam causing the holding switch lever to close in on 
either the raise or lower micro switch.
If there is a problem with one of the micro switches on the 
holding switch, the individual micro switch should not be 
replaced. Instead, the complete holding-switch assembly 
must be replaced. Replacement of an individual micro 
switch can cause alignment problems which will affect 
the operation of the tap-changer. Special fixtures are used 
to assemble the holding-switch assembly to ensure that 
alignment gap setting requirements are met.
Motor capacitor
The QD5 tap-changer motor uses a 50 μF, 440 Vac, and 
100°C motor capacitor. The motor capacitor is not part of 
the tap-changer assembly; it will be located in the voltage 
regulator control box.
Motor capacitor
Size  Rating
50 μ F,  440 Vac, 100°C for 50 and 60 Hertz 
It is recommended that a replacement capacitor be of the 
same size and rating as was originally supplied with the unit. 
Incorrectly sized motor capacitors can cause the motor to 
labor and not run properly or at all; premature motor failure 
will result.  Tap position tracking of the voltage regulator 
control will also be adversely affected by improperly sized 
motor capacitors.
Figure 2.  Motor capacitor.
Figure 3.  Holding switch assembly.
2
QD5 QUIK-DRIVE TAP-CHANGER INSTALLATION AND MAINTENANCE INSTRUCTIONS   MN225012EN   March 2016