8 type vsa12, vsa12b, vsa16, vsa20, and vsa20a operation and installation instructions  MN280063EN   May 2017
Accessories
Auxiliary switch
A one-, two-, three-, or four-stage auxiliary switch can be 
provided as an accessory. Each stage has two independent 
contacts that permit any desired combination of “a” 
(follow state of recloser contacts) and “b” (opposite state 
of recloser contacts) positions. The switch is wired to a 
separate terminal block as shown in Figure 5.
The switch contacts are insulated for 600 V and have a 
continuous current rating of 10 A. Their interrupting ratings 
are shown in Table 7.
Table 7. Auxiliary Switch Interrupting Ratings
 Volts
Inductive 
AC (amps)
Non-
Inductive 
AC (amps)
Inductive 
DC (amps)
Non-
Inductive 
DC (amps)
24 – – 15.0 20.0
48 – – 7.5 10.0
120 60 80 – –
125 – – 1.5 2.0
240 30 60 – –
250 – – 0.45 0.5
Current transformers
 WARNING
Hazardous voltage. The equipment is shipped with 
the shorting thumbscrews in the CT terminal blocks. 
These thumbscrews must not be removed until external 
connections are made to the terminal blocks. Energizing 
the equipment with the shorting screws removed, 
and no load connected, will cause high voltage to be 
generated in the CT secondaries. Contact with high 
voltage can cause severe personal injury or death and 
equipment damage. 
T208.2
Multi-ratio bushing current transformers can also be 
supplied in either 600:5 or 1200:5 A ratios. Each multi-
tapped CT secondary is wired to a separate six-point 
terminal block in the operator mechanism cabinet (Figure 5). 
The available current ratios and terminal block terminations 
are shown in Table 8.
Figure 6.  Position of shorting thumbscrews.
Figure 7 shows one of the three terminal blocks for the 
multi-ratio bushing CTs in the as-shipped condition. The 
secondary of each CT is shorted and grounded by the 
thumbscrew which shorts terminals X1 and X5 to the 
grounding bar. After external connections are made, the 
thumbscrew at X1 is removed and stored in the corner of 
the terminal block. The other thumbscrew remains in the 
grounding bar to make the common ground connection for 
one side of the CT secondary winding. The location of the 
screw in the bar is dependent upon the CT ratio desired and 
is always the higher of the two terminal numbers. Typical 
customer wiring to the three terminal blocks is shown in 
Figure 7.
Table 8.  Multi-Ratio Current Transformer Ratios and 
Terminal Connections
 600:5 Ratio BCT 1200:5 Ratio BCT Terminal Connection
600:5 1200:5 X1-X5
500:5 100:5 X2-X5
450:5 900:5 X3-X5
400:5 800:5 X1-X4
300:5 600:5 X2-X4
250:5 500:5 X3-X4
200:5 400:5 X4-X5
150:5 300:5 X1-X3
100:5 200:5 X1-X2
50:5 100:5 X2-X3
GRD    X5 X4 X3 X2  X1
GRD    X5 X4 X3 X2  X1
GRD    X5 X4 X3 X2  X1
GRD    X5 X4 X3 X2  X1
GRD    X5 X4 X3 X2  X1GRD    X5 X4 X3 X2  X1
Ground
Shorting
Screws
Common Return Connections
(Terminal X4 ground through shorting screws)
Permanently
Wired to CTs
Ground
Permanently
Wired to CTs
Shorting
Screws
Individually Wired Connections
Figure 7.  Position-shorting thumbscrews in terminal block and customer wiring.