1type vsa12, vsa12b, vsa16, vsa20, and vsa20a operation and installation instructions  MN280063EN   May 2017
Product information
Introduction
Service Information MN280063EN provides installation 
instructions, operating information, and testing procedures 
for Eaton’s Cooper Power™ series three-phase motor-
operated reclosers.
The information contained in this manual is organized into 
the following major categories: Safety Information, Product 
Information, Specifications and Ratings, Dimensions and 
Weights, Installation, Accessories, Operation, and Service 
Information.
Read this manual first
Read and understand the contents of this manual and follow 
all locally approved procedures and safety practices before 
installing or operating this equipment.
Additional information
These instructions cannot cover all details or variations 
in the equipment, procedures, or process described nor 
provide directions for meeting every possible contingency 
during installation, operation, or maintenance. For additional 
information, contact your Eaton representative.
Acceptance and initial inspection
This product is completely assembled, tested, and 
inspected at the factory. It is carefully calibrated, adjusted, 
and in good condition when accepted by the carrier for 
shipment.
Upon receipt, inspect the carton for signs of damage. 
Unpack the control and inspect it thoroughly for damage 
incurred during shipment. If damage is discovered, file a 
claim with the carrier immediately.
Handling and storage
Be careful during handling and storage of this equipment to 
minimize the possibility of damage. In particular, protect the 
bushings and control equipment.
If the unit is to be stored for any length of time before 
installation, provide a clean, dry storage area. If the recloser 
is to be stored in a humid atmosphere, make provisions to 
keep the cabinet heaters energized.
ANSI
®
 standards
The VSA recloser is designed and tested in accordance with 
ANSI
®
 standards: C37.60 and C37.85.
Quality standards
ISO 9001 certified quality management system
Description
A complete assembly consists of the recloser control unit, 
the vacuum interrupter assemblies, and the operating 
mechanism housing.
Recloser tripping employs stored spring energy. When the 
trip solenoid is actuated by the 24 Vdc trip signal, the stored 
spring energy is released to open the recloser. The 24 Vdc 
trip signal is originated at the recloser control. The 240 Vdc 
supply is not required to trip the recloser. An external 240 
Vac source is required to operate the drive motor. A 120 Vac 
input power supply accessory is also available.
Type VSA reclosers are electronically controlled by Eaton’s 
Cooper Power series recloser controls.