Explosion-protected empty enclosure GBXE
GB
8 Repairs / Overhaul / Modifications
Overhaul and repairs may only be carried out with genuine EATON /
Cooper Crouse-Hinds GmbH spare parts.
Repairs may only be carried out by EATON / Cooper Crouse-Hinds
GmbH or a qualified electrician (Competent person) in compliance
with the applicable national rules
(IEC/EN 60079-19).
For replacement and repair only original parts from EATON /
Cooper Crouse-Hinds GmbH may be used.
Modifications to the apparatus or changes of its design are not permitted,
except for the mounting of additional cable entries and the installation of
supply terminals in accordance with the approval of the apparatus.
9 Disposal/Recycling
When the apparatus is disposed of, the respective national regulations on
waste disposal will have to be observed.
In case of disposal you can obtain additional information from your EATON
/ Cooper Crouse-Hinds GmbH branch.
Subject to modifications or supplement of the product range.
10 Accessories / Spare parts
For accessories and spare parts, see EATON / Cooper Crouse-Hinds
GmbH catalogue.
6.2 Cable Entry
The minimum distance of the drillings is to be kept in accordance with the
table, drilling space for cable glands and stopping plugs.
Please contact EATON / Cooper Crouse-Hinds GmbH
All cable entry devices and blanking elements must be certified
for protection types ‘e’ and ‘tb’ and must have a minimum IP 66
rating.
All unused device openings must be fitted with a certified close-up
plug of protection types ‘e’ and ‘tb’ and must have a minimum IP 66
rating
The suitability of all entries should be considered in the end use
application.
For entries with parallel threads, cable glands, stop plugs must
be should be used along with additional seal or gasket.
6.3 Closing the device
Any foreign matter shall be removed from the apparatus.
Align the cover with the base.
Screw in the enclosure screws and tighten them diagonally
(test torque see technical data).
6.4 Taking into operation
Prior to taking the apparatus into operation, the tests specified in the
relevant national regulations will have to be carried out.
Apart from that, the correct functioning and installation of the enclosure /
equipment in accordance with these operating instructions and other
applicable regulations will have to be checked.
Electric plants must be examined by a qualified specialist before first
commissioning and regularly at specific intervals.
Incorrect installation and use can invalidate the guarantee.
7 Maintenance / Servicing
The relevant national regulations which apply to the maintenance/
repair of electrical apparatus in explosive atmospheres, will have to
be observed (IEC/EN 60079-17).
Before opening the enclosure make sure that the equipment is
disconnected from the voltage, or take the appropriate protective
measures.
In case of intrinsically safe circuits, working is permitted while voltage
applies.
The required maintenance intervals depend on the specific application and
will therefore have to be determined by the user dependent on the
conditions of use.
When servicing the apparatus, particularly those parts that are decisive for
the type of protection against explosion, will have to be checked (e.g.
intactness and tightness of the enclosure, efficacy of the gaskets and the
cable entries).
If during servicing, repairs prove to be necessary, section 8 of these
operating instructions will have to be observed.