32
RTK DB5
October 2016
INS DB5 Rev 9
Mining certification
Certification
Certified by EECS to Ex I M1 EEx ia 1
Certificate No: MECS01ATEX4260
Intrinsically safe parameters
DB-5-M-012:
Ui = 14.4V, Uo = 14.4V
Ci = 0, Li = 0
FM certification
Certification
Intrinsically Safe for Class I, Division 1, Groups A,B,C
and D.
Certificate No: J.I 3008604
Entity parameters for DB5 (24V version):
Vmax = 28VDC, Imax = 147mA, Pmax = 810mW,
Ci = 0, Li = 0
Entity parameters for DB5-12 (12V version):
Vmax = 15.7VDC, Imax = 150mA, Pmax = 560mW,
Ci = 0, Li = 0
CSA certification
Certification
Certified by CSA to standard numbers 0, 0.4, 0.5, 25, 30,
205. Class 1 Groups A,B,C and D
Certificate No: 79122
Supply
Min/max at terminals = 15-28VDC
Current (through interface) = 14mA
Environment
Operating temperature -20 to +55°C
Storage temperature -40 to +80°C
Humidity 5-95% RH, non-condensing
Protection IP65
Zener barrier interfaces
Contact Eaton for suitable MTL models
Galvanic isoloator interfaces
Contact Eaton for suitable MTL models