IB02602004E For more information visit: www.eaton.com
Instructional Literature
Effective: May 2008 Page 35
Instructions for the FP-6000 Protective Relay
4.6.2.1 Protection
Display 16. View Settings.
“Protection” Display:
Note: The number of setting groups that are displayed is programmable in the Configuration Settings as “# Set Grps.” The default # of setting groups
is 1, so this “display” will normally only show “Setting Group 1.” If “# Set Grps” is set to “4,” then all four setting groups will be displayed as shown
above. All four setting group’s sub-menus display the same settings, therefore only one example setting group is shown here.
“Phase Overcurrent” Display:
Protection
Setting Group 1
Setting Group 2
Setting Group 3
Setting Group 4
Setting Group 1
Phase Overcurrent
IX Measured OC
IR Residual OC
Unbalance Settings
Main V Protection
Aux V Protection
Neutral V Protection
Freq. Protection
Power Protection
Breaker Failure
Power Factor
Zone Interlocking
25 Sync Check
32V Var Trip
Thermal Protection
Alarms
Thermal Alarms
Phase Overcurrent
51P PH TOC Curve
51P PH TOC Setting
51P2 PH TOC Curve
51P2 PH TOC Setting
50P-1 PH IOC 1
50P-2 PH IOC 2
51P PH TOC Curve
Shape: MOD
Reset: Calc
Direction: Both
51P PH TOC Setting
Pickup (pu): 1.00
Time Mult: 1.00
50P-1 PH IOC 1
Pickup (pu): 2.00
Delay (c): 0
Direction: Both
51P2 PH TOC Curve
Shape: MOD
Reset: Calc
Direction: Both
51P2 PH TOC Setting
Pickup (pu): 1.00
Time Mult: 1.00
VRestraint: Disable
50P-2 PH IOC 2
Pickup (pu): 2.00
Delay (c): 0
Direction: Both