17
Switches, GHG 981,
industrial design up to 250 A, 3 and 6-pole
GB
1�8 Safety switch 160 A; GHG 981 0031 - 3-pole; GHG 981 0032- 6-pole
Rated voltage: 690 V, 50/60 Hz
Rated current: 160 A
Perm� short circuit back-up fuse: up to U
N
400 V up to U
N
500 V up to U
N
690 V
250 A/gL –- 200 A/gL
Switching capacity AC 23 A: 160 A 160 A 160 A
Cable entries (standard version): 3-pole version 6-pole version
2 x M63 + 1 x M25 4 x M50 + 1 x M25
suitable cables and test torques of the pressure screw
Cabel entry: M25 M50
Seal 1+2+3
(Ø mm / Nm)
min�
max�
(1)(2)
8�0 / 1�5
10�0 / 2�0
Seal 1+2
(Ø mm / Nm)
min�
max�
(1)(2)
10�0 / 2�3
13�0 / 2�6
24�0 / 6�0
28�0 / 7�0
Seal 1
(Ø mm / Nm)
min�
max�
(2)
13�5 / 1�3
17�5 / 2�3
28�0 / 5�0
35�0 / 7�0
Pressure screw (Nm) 3�0 7�5
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals: 1 x 16 - 95 mm² observe current load.
Test torque terminals: 6,0 Nm
Weight (standard version):
3-pole - approx� 7�50 kg 6-pole - approx� 14�00 kg
1�9 Safety switch 180 A; GHG 981 0031
Rated voltage: 690 V, 50/60 Hz
Rated current: 180 A
Perm� short circuit back-up fuse: up to U
N
400 V up to U
N
500 V up to U
N
690 V
250 A/gL – 200 A/gL
Switching capacity AC 3: 180 A 150 A 125 A
Cable entries (standard version): 3-pole version
2 x M63 + 1 x M25
suitable cables and test torques of the pressure screw
Cabel entry: M25 M63
Seal 1+2+3
(Ø mm / Nm)
min�
max�
(1)
8�0 / 1�5
10�0 / 2�0
Seal 1+2
(Ø mm / Nm)
min�
max�
(1)
10�0 / 2�3
13�0 / 2�6
29�0 / 12�0
35�0 / 12�0
Seal 1
(Ø mm / Nm)
min�
max�
(1)
13�5 / 1�3
17�5 / 2�3
36�0 / 12�0
41�0 / 13�0
Pressure screw (Nm) 3�0 7�5
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals:
2 x 4�0 - 70 mm² observe current load.
max� 1 x 120 mm² (Use cable lugs supplied with switches)
Test torque terminals: 5�0 Nm
Weight (standard version): 3-pole - approx� 16�50 kg
160 A 3-pole
180 A 3-pole
160 A 6-pole
X = fixing dimensions
Dimensions in mm