18
Switches, GHG 981,
industrial design up to 250 A, 3 and 6-pole
GB
1�10 Safety switch 250 A; GHG 981 0033
Rated voltage: 690 V, 50/60 Hz
Rated current: 250 A
Perm� short circuit back-up fuse: up to U
N
400 V up to U
N
500 V up to U
N
690 V
350 A/gL –- 300 A/gL
Switching capacity AC 23 A: 250 A 250 A 250 A
Cable entries (standard version): 3-pole version
Double cable end box +M25 2 x Ø 46 -72mm + 1 x M25
suitable cables and test torques of the
pressure screw M25
Ø Nm
Seal 1+2+3
(Ø mm / Nm)
min�
max�
(1)
8�0
10�0
1� 5
2�0
Seal 1+2
mm / Nm)
1 2
3
min�
max�
(1)
10�0
13�0
2�3
2�6
Seal 1
mm / Nm)
1 2
3
min�
max�
(1)
13�5
1 7� 5
1� 3
2�3
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry
Test torque for escrew in thread cable entry
3�0 Nm
Terminals: 1 x 35 - 120 mm² observe current load.
Test torque terminals:
6�0 Nm
Weight (standard version): 3-pole - approx� 16�0 kg
1�11 Auxiliary contacts
Safety switch 10 A 20-80/125-180 A 100,160,250 A
Rated voltage: 500 V 690 V 690 V AC
Rated current: 10 A 25 A 6 A
Perm� short circuit back-up fuse: 16 A/gL 25 A/gL 6 A/gL
Switching capacity:
AC 15
230 V
6�0 A 8�0 A 6�0 A
400 V 4�0 A 6�0 A 4�0 A
DC 13
24 V
2�0 A 6�0 A 1�0 A
230 V 0�5 A 0�4 A 0�3 A
Versions with gold-tipped contacts: 400 mA 400 mA 400 mA
Terminals: 2x1�5-2�5mm² 2x1�5-4�0mm² 1x0�75-2�5mm²
250 A 3-pole
X = fixing dimensions
Dimensions in mm