6
Instruction Leaflet IL29C092E
Eective November 2013
Installation Instructions for KD, HKD, KDC, CKD
CHKD, Circuit Breakers with Digitrip OPTIM
Trip Unit and Powernet and/or Zone Interlock
EATON CORPORATION www.eaton.com
Table
2
-
1
Terminal
Types
Terminal Terminal Screw
AWG
Wire Torque
Cat.
No.
Material Head Wire Wire Type Value
Body Type Range Range Ib
-
in
Aluminum Socket 35
-
185 275 (31)
Aluminum Socket 120
-
240 375 (42)
Socket 275 (31)
K Aluminum Socket 275 375
or or (31
375 (42)
Socket 240
-
300 550 (62)
Socket 35
-
185 Cu Only 275 (31)
Copper Socket 120
-
240 375 (42)
Copper Socket Cu Only 275 (31)
CAUTION
WHEN ALUMINUM CONDUCTORS ARE USED, THE
APPLICATION OF A SUITABLE JOINT COMPOUND
IS
RECOMMENDED TO REDUCE THE POSSIBILITY
OF TERMINAL OVERHEATING. OVERHEATING
CAN CAUSE NUISANCE TRIPPING AND DAMAGE
TO THE CIRCUIT BREAKER.
Table
2
-
2
Rating Plugs
2
-
11. When step
-
type terminals (TA400K, TA401K,
TA402K or T400K) are used, terminal shields (supplied
with terminals) must be installed on the circuit breaker
(Figure 2
-
4). Warning label supplied with the kit must
be attached to the circuit breaker cover.
WARNING
HAZARDOUS VOLTAGE CONDITIONS CAN CAUSE
DEATH OR SEVERE PERSONAL INJURY. MAIN
-
TAIN ORIGINAL ELECTRICAL CLEARANCE AND
CREEPAGE SPACINGS AT TERMINATIONS.
2
-
12. Connect the control wires and power wires to their
appropriate locations on the male plug of the terminal
block, see Figure 2
-
5. Control power is necessary if
IMPACC communication is required.
2
-
13. Install an appropriate rating plug, see Table 2
-
2.
2
-
14. Plug in the hand held Digitrip OPTIMIZER into the
programming port and set the INCOM address. Then
set the various trip unit current settings using the OPTI
-
MIZER, or when INCOM is available, use the circuit
Connect line and load conductors and accessory
leads.
When a dual conductor terminal (Catalog
No.
TA402K, TA401K, TA400K or T400K is installed on
the circuit breaker and
a
single conductor is used,
the conductor should be installed in the terminal
opening nearest to the circuit breaker terminal
mounting conductor.
2-8. Install the supplied neutral current sensor in the
neutral pole of a four
-
wire system, see Figure 2
-
6.
2-9. After the circuit breaker is installed, check all
mounting hardware and terminal connecting hardware
for correct torque loading. Torque values for line/load
terminals are given in Table 2
-
1 and on the circuit
breaker nameplate.
2
-
1 0. If required, install line terminal cover on circuit
breaker cover with mounting slots provided.
13
tapped
Figure
2
-
6
Neutral Sensor Dimensions