Instruction Booklet IB01900001E
Effective August 2017
Instructions for Magnum DS Metal-Enclosed
Low-Voltage ARC Resistant Switchgear Assemblies
EATON www.eaton.com
Figure 16. Typical Exhaust Clearance Zone.
3.7 Cable Compartment
The cable compartment is designed to allow both top and bottom
entry of cables. Several different methods can be used when pen-
etrating the top roof sheet and/or bottom pan. Conduit compression
hubs are the preferred method to limit potential arcing gases from
escaping the equipment. When this type of hub is not used, other
types of cable fittings can be used, but it is the installer’s respon-
sibility to seal any openings, up to ¾ in. with duct seal. Openings
larger than ¾ in. are not allowed. When conduit stub ups are used,
in a slab, the bottom pan must have holes cut into it to allow the
conduit to pass through while maintaining the no larger than ¾ in.
gap requirement
RESTRICTED AREA
AROUND EXHAUST
DUCT EXIT OF 4 FEET
Section 4: Additional Publications
In addition to this Instruction Book, the following Instruction Books
and drawings are commonly included with any Magnum DS Circuit
Breaker and/or provided with any Eaton Low-Voltage Assembly ship-
ment. Please inspect the documentation provided before contacting
an Eaton service representative for replacements.
IB 2C12060H08 Instructions for Installation, Operation and
Maintenance of Magnum DS, DSX and DSL Low
Voltage Power Circuit Breakers
IB 01901001E Instructions for Magnum DS Metal-Enclosed Low-
Voltage Assemblies
4A37896 Magnum DS Structure Base Plan