Double-wide Fixed
Standard Frame Fixed
Narrow Frame Fixed
Instructions for Installation, Operation and Maintenance of
Magnum DS, DSX and DSL Low Voltage Power Circuit Breakers
I.B. 2C12060H08 Supersedes I.B. 2C12060H07 dated April 2005
Effective May 2006
IB2C12060H08
For more information visit: www.EatonElectrical.com
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers

  • H
    Holly SmithAug 7, 2025
    What to do if the Eaton MDS-625 Power Tool circuit breaker trips open?
    • S
      Stacy JordanAug 7, 2025
      If the Eaton Power Tool circuit breaker trips open, it could be due to several reasons. First, ensure the rating plug is installed and corresponds to the current sensors. If the breaker trips repeatedly due to transient current, allow the breaker and loads to cool before re-closing. Finally, an overload or fault current condition may be present. Use the status and fault indicators to locate and remove the overload or fault.
  • S
    Sarah PerezAug 21, 2025
    Why does my Eaton MDS-625 circuit breaker open if the fault trip indicator button is not out?
    • D
      David ProctorAug 21, 2025
      If your Eaton Power Tool circuit breaker opens and the fault trip indicator button is not out, several factors could be at play. It might be due to undervoltage release operation; in this case, check and correct the UVR supply voltage to be within 85-110% of the rated voltage. Alternatively, the shunt trip may be operating, so check the control signals to the shunt trip and correct if necessary. If neither of these is the cause, the trip latch may be defective, so inspect its condition and engagement before closing.

Summary

Introduction and Safety

Safety Practices

Essential safety procedures for installation, operation, and maintenance.

Qualified Personnel

Requirements and qualifications for personnel working on circuit breakers.

Receiving, Handling, and Installation

Installing Drawout Circuit Breaker

Step-by-step guide for installing drawout circuit breakers into cassettes.

Circuit Breaker Description and Operation

Electronic Tripping System

Overview of the microprocessor-based trip unit, sensors, and actuator.

Drawout Circuit Breaker and Cassette

Inspection and Maintenance

General

General guidelines and warnings for inspection and maintenance.

What to Inspect

Detailed inspection points for various breaker components.

Troubleshooting Common Issues

Eaton MDS-625 Specifications