Instructions for Installation, Operation and Maintenance of
Magnum DS, DSX and DSL Low Voltage Power Circuit Breakers
I.B. 2C12060H08 Supersedes I.B. 2C12060H07 dated April 2005
Effective May 2006
IB2C12060H08
For more information visit: www.EatonElectrical.com
www . ElectricalPartManuals . com

Table of Contents

Questions and Answers

  • T
    Tony FowlerAug 6, 2025
    What to do if the Eaton Power Tool circuit breaker trips open?
    • C
      Courtney SteeleAug 6, 2025
      If the Eaton Power Tool circuit breaker trips open, it could be due to several reasons. First, ensure the rating plug is installed and corresponds to the current sensors. If the breaker trips repeatedly due to transient current, allow the breaker and loads to cool before re-closing. Finally, an overload or fault current condition may be present. Use the status and fault indicators to locate and remove the overload or fault.
  • K
    Karl AllenAug 22, 2025
    Why does my Eaton MDS-820 circuit breaker open if the fault trip indicator button is not out?
    • E
      egonzalezAug 22, 2025
      If your Eaton Power Tool circuit breaker opens and the fault trip indicator button is not out, several factors could be at play. It might be due to undervoltage release operation; in this case, check and correct the UVR supply voltage to be within 85-110% of the rated voltage. Alternatively, the shunt trip may be operating, so check the control signals to the shunt trip and correct if necessary. If neither of these is the cause, the trip latch may be defective, so inspect its condition and engagement before closing.

Summary

Purpose and Safety Information

General Safety Requirements

Emphasizes adherence to safety codes, standards, and regulations during installation and operation.

Warning Labels and Presentation

Explains the style of warning labels to ensure personnel are alert to safety precautions.

Inspection, Troubleshooting, and Renewal Parts

Inspection and Maintenance Overview

Introduces inspection and maintenance requirements for Magnum circuit breakers.

Troubleshooting Guide Introduction

Introduces the troubleshooting section and lists resources for assistance.

Introduction to Magnum Circuit Breakers

Safety Features and Practices

Highlights built-in safety features and essential practices for safe operation.

Receiving, Handling, and Installation

Breaker Inspection and Drawout Installation

Outlines visual inspection steps and the process for installing drawout circuit breakers.

Rejection Interlocks and Positioning

Explains the function of rejection interlocks and the four normal positions for drawout breakers.

Levering Circuit Breakers

Describes the procedure for levering circuit breakers into TEST or CONNECT positions.

Fixed Circuit Breakers and Operation

Initial Operation Checks

Outlines initial operation checks for circuit breakers before they are put into service.

Electronic Tripping System

Overview of Tripping System

Describes the three-part electronic tripping system: trip unit, sensors, and actuator.

Rating Plug and Current Sensors

Explains the function and importance of rating plugs and current sensors.

Trip Actuator and Special Options

Details the trip actuator, mechanical trip flag, making current release, and high instantaneous trip.

MDSL Limiters and Blown Limiter Indication

MDSL Current Limiters

Explains the application, selection, and replacement of MDSL integral current limiters.

Fixed Circuit Breakers

Inspection and Maintenance

Troubleshooting