MEM
Memera
Consumer unit
Important notes
1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician
in accordance with current electrical engineering Codes of Practice, Regulations for the Electrical equipment of
Buildings (BS7671), HSG224 – Construction (Design and Management) Regulations 1994, HSG150 – Health and
Safety in Construction, Statutory requirements and any Specifi c instruction issued by the Company.
2. After completing the installation and testing of this product it is essential that this leafl et is drawn to the attention of
the person responsible for its future operation and maintenance, and is at all times available for ready reference.
3. These notes assume throughout that the product is disconnected from the supply.
It is essential that this is done before any work is carried out.
1. This Consumer Unit must be installed by a competent person in accordance with BS7671 IEE Regulations for
electrical Installations with the requirements of all relevant legislation, and Accepted practices in the industry.
2. The total current supplied by the Consumer Unit must not exceed the rating of the incoming
main switch, RCD or any additional limitations (as shown on the Way Labels).
3. This board is suitable for indoor use only and is rated at IP40.
4. Ambient Temperature Conditions:
The MCB’s are calibrated to meet 35°C according to requirements laid down in IEC/EN60898. For other
temperatures the following rating factor should be used: 60°C - 0.85, 20°C - 1.0, 0°C - 1.1
5. All components used in the EATON MEMERA CONSUMER UNIT must be supplied by or approved by EATON. The use of any
other components within the EATON MEMERA CONSUMER UNIT will negate any warranty issued by EATON ELECTRIC LTD.
6. The consumer unit and appropriate devices have been type tested to the following specifi cations:
MCB’s IEC/EN 60898
RCCD’s IEC/EN 61008-1
RCBOs IEC/EN 61009-1
Main Switch IEC/EN 60947-3
Consumer Unit IEC/EN 60493-3