48
10 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN March 2019 www.eaton.com
10.2.29 PDG4 PXR25 and 20D settings
Frame 800A All All 800 A G styles
Profile Long delay Short delay Instantaneous Ground
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup (Isd)
Isd =nx (lr)
Time (tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx (In)
Time (tg)
tg (s)
Min
320 0.5 1.5 0.050 2 0.2 0.100
Max
800 24 8.0 0.500 8.5 1.0 1.000
Min
0.5 0.067 0.2 0.067
Max
7 0.300 1.0 0.300
Step
10 0.10 0.10 0.010 0.10 0.010 0.010
Add'l opt
OFF OFF
I
2
t Flat Instantaneous override Trip Flat
I
4
t I
2
t 6800 A Alarm I
2
t
10.2.30 PDC4 PXR25 and 20D settings
Frame 800 A 1000 A All All 800 A 1000 A G styles
Profile Long delay Short delay Instantaneous Ground
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup (Isd)
Isd =nx (lr)
Time (tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx (In)
Time (tg)
tg (s)
Min
320 400 0.5 1.5 0.050 2 2 0.2 0.10 0
Max
800 1000 24.0 8.0 0.500 17.6 11 1.0 1.000
Min
0.5 0.067 0.2 0.067
Max
7 0.300 1.0 0.300
Step
10 10 0.10 0.10 0.01 0.10 0.10 0.01 0.01
Add'l opt
OFF OFF
I
2
t Flat Instantaneous override Trip Flat
I
4
t I
2
t 4400 A Alarm I
2
t
10.2.31 PDG5 PXR20 settings
Frame 800 A 1200 A 1600 A IEC 800 A 1200 A 1600 A IEC All 800 A 1200 A 1600 A IEC G styles
Profile Long delay Short delay Instantaneous Ground
Dial Ir (A) Tr(S)@6x Ir Isd (x lr) tsd (s) Ii (x In) Ig (x In) tg (s)
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup
(Isd)
Isd =nx
(lr)
Time
(tsd)
tsd (s) Pickup li = nx (In)
Pickup
(Ig)
lg = nx
(In)"
Time (tg)
tg (s)
1
320 500 800 0.5 0.5 0.5 1.5 0.050 2 2 2 0.2 0.100
2
350 550 900 1 1 1 2.0 0.10 0 3 3 2.5 0.3 0.150
3
400 600 1000 2 2 2 3.0 0.150 4 4 3 0.4 0.200
4
450 630 1100 4 4 4 4.0 0.200 5 5 3.5 0.6 0.300
5
500 700 1200 7 7 7 5.0 0.300 6 6 4 0.8 0.500
6
550 800 1250 8 10 10 6.0 0.400 8 7 5 1.0 0.750
7
600 900 1300 10 12 12 8.0 0.500 10 8 6 0.2 1.000
8
630 1000 1400 12 15 15 10.0 0.067 12 9 7 0.5 0.067
9
700 1100 1500 13 20 18 12.0 0.150 15 10 8 1.0 0.150
10
800 1200 1600 14 24 20 OFF 0.300 18.0 12.0 9 OFF 0.300
Flat Instantaneous override Trip Flat
I
2
t 14400 A Alarm I
2
t
Pickup (Isd) limited by Max Instantaneous