49
10 Available protection settings
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN March 2019 www.eaton.com
10.2.32 PDG5 PXR25 and 20D settings
Frame 800 A 1200 A 1600 A IEC 800 A 1200 A 1600 A IEC All 800 A 1200 A 1600 A IEC G styles
Profile Long Delay Short Delay Instantaneous Ground
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup
(Isd)
Isd =nx (lr)
Time
(tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx
(In)
Time
(tg)
tg (s)
Min
320 500 800 0.5 0.5 0.5 1.5 0.050 2 2 2 0.2 0.100
Max
800 1200 1600 14.0 24.0 20.0 8.0 0.500 18 12 9 1.0 1.000
Min
0.5 0.5 0.5 0.067 0.2 0.067
Max
7 7 7 0.300 1.0 0.300
Step
10 10 10 0.10 0.10 0.10 0.10 0.01 0.10 0.10 0.01 0.01
Add'l
opt
OFF OFF
I
2
t I
2
t I
2
t Flat Instantaneous override Trip Flat
I
4
t I
4
t I
4
t I
2
t 14400 A Alarm I
2
t
10.2.33 PDG6 PXR20 settings
Frame 1600 A 2000 A 2500 A IEC All 1600 A 2000 A 2500 A IEC All 1600 A 2000 A 2500 A IEC G styles
Profile Long delay Short delay Instantaneous Ground
Dial Ir (A)
Tr(S)
@6x Ir Isd (x lr) tsd (s) Ii (x In) Ig (x In) tg (s)
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup (Isd)
Isd =nx (lr)
Time
(tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx(In)
Time
(tg)
tg (s)
1
700 1000 1600 0.5 1.5 1.5 1.5 0.050 2 2 2 0.2 0.100
2
800 1100 1700 1 2.0 2.0 2.0 0.100 3 3 2.5 0.3 0.150
3
900 1200 1800 2 3.0 3.0 2.5 0.150 4 4 3 0.4 0.200
4
1000 1250 1900 4 4.0 4.0 3.0 0.200 5 5 3.5 0.6 0.300
5
1100 1400 2000 7 5.0 5.0 3.5 0.300 6 6 4 0.8 0.500
6
1200 1600 2100 10 6.0 6.0 4.0 0.400 7 7 4.5 1.0 0.750
7
1250 1700 2200 12 7.0 7.0 4.5 0.500 8 7.5 5 0.2 1.000
8
1400 1800 2300 15 8.0 8.0 5.0 0.067 9 8 6 0.5 0.067
9
1500 1900 2400 20 9.0 9.0 6.0 0.150 10 8.5 7 1.0 0.150
10
1600 2000 2500 24 OFF OFF OFF 0.300 10.94 8.75 7.0 0 OFF 0.300
Flat Instantaneous override Trip Flat
I
2
t 17500 A Alarm I
2
t
Pickup (Isd) limited by Max Instantaneous
Note that ground fault pickup will not exceed 1200 A.
10.2.34 PDG6 PXR25 and 20D settings
Frame 1600 A 2000 A 2500 A IEC All 1600 A 2000 A 2500 A IEC All 800 A 1200 A 1600 A IEC G styles
Profile Long delay Short delay Instantaneous Ground
Setting Pickup Ir (amps)
Time (s)
at 6x (Ir)
Pickup (Isd)
Isd =nx (lr)
Time
(tsd)
tsd (s) Pickup li = nx (In)
Pickup (Ig)
lg = nx (In)
Time
(tg)
tg (s)
Min
700 1000 1600 0.5 1.5 1.5 1.5 0.050 2 2 2 0.2 0.100
Max
1600 2000 2500 24.0 9.0 9.0 6.0 0.500 10.94 8.75 7.00 1.0 1.000
Min
0.5 0.067 0.2 0.067
Max
7 0.300 1.0 0.300
Step
10 10 10 0.10 0.10 0.10 0.10 0.01 0.10 0.10 0.10 0.01 0.01
Add'l
opt
OFF OFF OFF OFF
I
2
t Flat Instantaneous override Trip Flat
I
4
t I
2
t 17500 A Alarm I
2
t
Pickup (Isd) limited by Max Instantaneous
Note that ground fault pickup will not exceed 1200 A.