66
11 Modbus register map
PXR TRIP UNITS FOR POWER DEFENSE MOLDED CASE CIRCUIT BREAKERS MN012007EN March 2019 www.eaton.com
Remote Control Date Format (continued)
Control
Group Definition Password
Hex byte Hex word
0x6202 0x6201 0x6200 0x6202 0x6201 0x6200
Byte 5 Byte 4 Byte 3 Byte 2 Byte 1 Byte 0 Word 3 Word 2 Word 1
Reset Reset trip No FF FF FD 00 00 02 FFFF FD00 0002
Reset min/max currents Yes FF FE F2 00 01 0D FFFE F200 010D
Reset min/max line-to-
neutral voltages
Yes FF FE F0 00 01 0F FFFE F000 010F
Reset min/max line-to-line
voltages
Yes FF FE F1 00 01 0E FFFE F100 010E
Reset peak demand watts Yes FF FF FB 00 00 04 FFFF FB00 0004
Reset all min/max values Yes FF FE FB 00 01 04 FFFE FB00 0104
Reset energy Yes FF FF F7 00 00 08 FFFF F700 0008
Reset trip count Yes FF FA FE 00 05 01 FFFA FE00 0501
Reset operations count Yes FF FE FD 00 01 02 FFFE FD00 0102
Reset temperature Yes FF FA FD 00 05 02 FFFA FD00 0502
Reset runtime Yes FF FE FC 00 01 03 FFFE FC00 0103
Reset all diagnostics
information
Yes FF FA FC 00 05 03 FFFA FC00 0503
Reset powered up
indication
No FF FF FC 00 00 03 FFFF FC00 0003
Open breaker Yes FE FF FF 01 00 00 FEFF FF01 0000
Maintenance
Mode
Enable maintenance mode No FE FF F7 01 00 08 FEFF F701 0008
Relay Output Disable maintenance mode No FE FF F6 01 00 09 FEFF F601 0009
Activate relay output 1 No FB FE FE 04 01 01 FBFE FE04 0101
De-activate relay output 1 No FB FD FE 04 02 01 FBFD FE04 0201
Activate relay output 2 No FB FE FD 04 01 02 FBFE FD04 0102
De-activate relay output 2 No FB FD FD 04 02 02 FBFD FD04 0202
Activate relay output 3 No FB FE FC 04 01 03 FBFE FC04 0103
De-activate relay output 3 No FB FD FC 04 02 03 FBFD FC04 0203
11.3.7 Date and time
Trip unit supports Modbus master read real-time clock information. Eight registers, starting
from register number 402921 are reserved for this information, as defined in 0. Detailed
information is listed in 0. User could set system time through function code 16.
Definition Modbus register number Modbus register address Data range
Month 402921 0x0B68 1-12
Day 402922 0x0B69 1-31
Year 402923 0x0B6A 2000-2099
Day of week 402924 0x0B6B 1=Sunday…7=Saturday
Hour 402925 0x0B6C 0-23
Minute 402926 0x0B6D 0-59
Second 402927 0x0B6E 0-59
1/100th second 402928 0x0B6F