5
OPTIONS
MENU
u
u
u
u
OPERATING 
HOUR
EXT INPUT
LANGAGE
PIN
FACTORY 
SETTINGS
INFO
NO PIN
WITH PIN CURRENT PIN
NEW PIN
00:00
Setting manual or permanent switching
Manual and permanent switching can be set using the menu 
in MANUAL or (in the automatic screen) by key combination 
(see g).
 •
Manual control 
Reversing the channel status to the next automatic or 
programmed switching.
 •
Permanent switching 
As long as a permanent switching (on or off) is activated, 
the programmed switching times are ineffective.
Activate manual switching
 Briey press both keys simultaneously
Activate permanent switching
 Simultaneously press both keys for 2 seconds 
Cancelling manual/permanent switching
 Press both keys simultaneously
Operating hour counter
The operating hours of the channel (relay) are displayed and 
deleted in the OPTIONS menu. If the number of operating 
hours exceeds the value set in the Service menu, SERVICE will 
appear in the display. 
Example: Replace a lamp after 5,000 h. 
 Delete operating hours or set a higher value in Service (e.g. 
to 10,000 h)
Resetting the time switch
 Press the 4 buttons simultaneously.
 ▻ You can choose between RETAIN PROGRAM and DELETE 
PROGRAM.
6.  Technical Data
Operating voltage: 230 V AC +10 % / –15 %
Frequency: 50–60 Hz
Standby: 0,4 W
Max switching capacity.: 16 A (at 250 V AC, cos ϕ = 1)
Switching capacity: 10 A (at 250 V AC, cos ϕ = 0,6)
Min. switching capacity: 10 mA/230 V AC
100 mA/24 V AC/DC
Switch output:  switching of any phase is 
permitted
TSDW1COA-1: suitable for switching SELV (Safe 
Extra-Low Voltage)
Protection rating: IP 20  in accordance with  
EN 60529
Protection class: II in accordance with EN 
60730-1 subject to designated 
installation
Operating temperature: –30 °C … +60 °C
Power reserve:  10 years at +20 °C
Switching accuracy: accurate to the second
Time accuracy (typical) ± 0,25 s/day (25 °C)
Rated impulse voltage 4 kV
Pollution degree 2
Software class: A
Contact two way switch, contact µ
Max. switching cycles with 16 A resistive 
load 
50 000
Incandescent lamp load 2600 W
Halogen lamp load 2600 W
Fluorescent lamps (LLB low-loss bal-
lasts): 
uncorrected 
series-corrected 
parallel-corrected
2600 VA
2600 VA 
1300 VA (130 µF)
Compact uorescent lamps (EB) 1100 W
LED-lamps (< 2 W)  50 W
LED-lamps (> 2 W)  600 W
 L The time switch display is only fully functional at tempera-
tures from +5 °C - +55 °C.